A 150KW 440V motor is need to replace in the field instead
of faulty one. what are the main parameter should I need to
check?

Answer Posted / a.p.nanjappa

150kw , 440 is a large motr. the starting current of this
induction motor will be 5-8 times depend on drive ex-fan.
and coast for 6-8s to attain full speed.
so, the new contactor shall be good quality , with
overload,instantaneous with time delay shall be selected.
Reverse rotation protection, vibrations,
Unbalnced current protection optional.
LV power cable terminal box cable connection and support.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is meant by rotating magnetic filed

1524


I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?

2574


hi, in the event earth grounding is not available in a project, is there any other way to make the elcb work? fyi, i have an instant water heater (6.5kw) installed, however if there is grounding in the heating element inside the heater assembly, i will get grounded. thank you in advance to those who will answer my question.

1512


Where is servomechanism used?

657


hr round

1654






I have a relay contact rated at 220v dc which is supplied with a 24vdc from the panel,for it to trip the dampers(24vdc).What if the application of the relay changes so that it should work at its rated 220vdc then will it work at 24vdc supply given or any other consideration needs to be taken .....

1643


Meter p.t. ratio= 3×230/400 , c.t.ratio = 3×1 (2) A what is m.f.

1318


Pl.brief me any electrical major fault you have rectified.

1484


WHAT KIND OF LIGHTENING PROTECTION SCHEMS CAN BE ADOPTED FOR THE FLAT ROOF OF BIG DIMENSION.

1628


what is the profesional board for electrical engineer what is thepast and during construction for electrical engineering

1460


why ahould you show client/engineer activities clearly on the project plan

2335


In single phase capacitor motor, if the motor rotate reverse direction then how much power will be consumed by the motor and why?

1466


in a solar power plant,we are going to step up the voltage 350V to 33kv, and to 132kv GSS. i want to ask that if it is possible that 315v/33kv is not possible because we also use 315v/11kv. or it should be 415v/33kv? is it effects generation or losses?  the second question is-generation is depends on LV winding? or LV winding design for generation voltage?

1286


What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?

1758


how to size H.T & L.T Panel ?

1634