On a 10 KVA UPS we have to provide a DC MCB for Battery bank
of 16 nos (12 V 65 AH).
What Shall be the current rating of DC MCB ?
Answer Posted / asif.k64@hotmail.com
UPS is 10 KVA, and battery is 65AH
Hence if it is a 1 phase UPS
KVA = V*A
10000 = 240*A
A= 10000/240
A = 42 A full load
Approximately a 63 A MCB would be required
| Is This Answer Correct ? | 21 Yes | 7 No |
Post New Answer View All Answers
Why we are using only Dyn11 tranformer in distribution system but not using a Dyn1 in distributing system?why not and advantage and disadvantage in both
what are the specifications we must look at to select a relay for any capacity motor?
Define closed loop control system.
What are the insulation standerds for eg H clase and how many insulation standerds are there and its standerds??????
design a 3 bit synchronous and asynchronous counter using T- flipflop
can i use 2000/5A Clamp meter to measure HT cable
Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?
WHAT IS DOL STARTER? HOW IT WORK? GIVE ITS CONTROL AND POWER DIAGRAM .
Advantages of using generator circuit breaker (GCB) scheme in a power station ?
how to find the multiplication factor for digital energy meter and analog energy meter
which model T or pie model is prefarable in power syatem
what is differant beetween overload current and phase current?
Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar
ELECTRICAL DRIVES: can a motor load system with passive load torque can have equilibrium speed in second quadrant
what is the carona effects meaning in HT line transmmission system