How can we parallel two transformer with vector gorup YNd11
and YNd1?How is connection two transformer GT?
Answer Posted / engr. l. o. osuji
It is advised not to parallel the two transformers because
of the difference in their phase shifts. For YNd11 the HV
lags the LV by 30 degrees while in YNd1 the HV leads the LV
by 30 degrees. Parallelling the two will lead to over
heating and other abnormal conditions which may lead their
protective relays to malfunction.
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
What are the special cables required for explosion proof wiring?
What conditions are required for transformer to operate at low frequencies ?
why there using acb enclosure in big buildings
In single phase ac ups supply when current is measured with tong tester neutral current is found more than phase current.What is the reason?
A TRANSFORMER 440/400V,DELTA/STAR CONNECTED.THE NEUTRAL CONNECTED WITH GROUND CABLE THAT IS DIRECTLY CONNECTED TO THE PANEL,FROM PANEL IT IS CONNECTED EARTH PIT.IS IT RIGHT? IF IT IS RIGHT LEAKAGE CURRENT AFFECTED.SECONDATY IS PROTECTED WITH EARTH LEAKAGE RELAY.
What is milivolt dop test in Busducts? What is its significance & procedure to do the test?
Difference between transition and diffusion capacitance
what is p.s impedance measurement test in earthing transformer?
sir i am apearing for nic exam.i dont know exam pattern.can you please send me some model papers
1. What is the exact formula for one weber? for example,(one ampere = one coulomb electron of electrons crossing a point of conductor at one second. i.e, 1A=1Q/1sec)
what is settable hystersis protection? If any body knows plz kindly post the answer..
How can we calculate cable size in Low voltage & high voltage
What is the operating principle of turbo-generator.
we have a lot of model of rectifier but thyristor rectifier is the most rectifier that use in power system. Do you know why this rectifier is used?
Define damping ratio.