how we can measure the interface level?is it possible to
measure interface level with dp or pressure transmitter?
Answer Posted / m m chotrani
Yes we can measure interface level by purge method.you can
use two purges (sensors of ss pipe generally 1/4"NB).Now
for interface measurement two liquids of different
densities should be there. suppose the interphase takes
place between 300 and 450 mm height from the bottom of the
tank.now the interface be 50%. height difference (probe
distance is 150 mm. multiply 150 withe density of 1st
liquid say 0.8 gm/cc.which will be 120mm. and multiply 150
with the density of another liquid with the density say 1.2
gm/cc which is 180 mm.So your transmitter range is 120-180
mm of water column. calibrate the transmitter for this
range and connect both the probes to HP and LP connections
of transmitters
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
Speedtronic system .
send me HPCL paper
Definition of reverse and acting controllers:
pls suggest suitable MOC of diaphragm for pressure measurement of UREA grade solution service fluid.
what is output of FOUNDATION FIELD BUS transmitter
What is the principle of capacitance type level transmitter?
what is the procedure of belt scale calibration?
How to Calibrate Interface Level Troll in field
How to calibration a control valve?
hi friends,im an instrumentation and contol engg student,can u hlp me of suggsting barc written question paper,my id is roysuvaranjan@gmail.com, cel no.9563591747
What is surge and how is it prevented, what is the purpose of bypass valve across AS valve.
Draw a great bridge circuit.
What are different types of control valves?
We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.