why we connect the capacitor bank in star , not in delta in
any system
Answer Posted / nishant2110
You are mistaken my friend,
Most of the time, we use DELTA capacitor bank in parallel to
the line to improve pf.
Actually
1. Delta connection provides 3 times more reactive power(kVAR)
than star.
2. less heat loss in delta
3. less triplen harmonic in delta
force to use delta over star capacitor bank.
Allthough, there are few instances where we use ungrounded
star connection but that is very rare.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
I want to design a heating coil of 80/20 nicrome for 3.5KW please give me the calculations choosing for physical dimensions assume coil voltage will be 110V AC assume necessary conditions
new 90kw motor installed so how I purchased cable ,fuse,etc please give me technic for cable selected why always capacitor delta connection
distribution is maximum done by a)radial b)network c) parallel d)b & c
What is the lockout relay
what is the grounding Calculation formula? spouse i want to provide grounding to 3phase 18kw motor or i want to provide ground to 3phase 10kva dry type transformere or you give me any exemple...... Thanks.
How harmonic block test are conducted on relays ( Siemens,Areva ect )power transformer using omicron kit?
Why we use auxillary relay ? what is function of differential relay, directional o/c relay?
What must be the minimum distance maintained between 2 Generators as per International standards?
which of the following elements is not present in stainless steel
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
What is the types of HT motor testing
Briefly describe means used by electricity suppliers to influence the flow of active and reactive power in power networks (one for each type)?
hello if any one have papers vof hpcl or sail, plz send me
when we have to use UPF wattmeter and LPF wattmeter? what is the difference between UPF and LPF wattmeter in terms of construction?
I have 4 DG set with 1500KVA rating. system breakers are 11KV & alternator are 415 Volts. Between alternator & breaker one stepup transformer used. i want to Know what is max. resistance for body earthing & 415 & 11KV V Neuteal earthing. my fault current is 14 times for 2 sec.