how to rectify the problem ,if we erected the DPT instrument
wrongly of hp on lp side and lp on hp side?
Answer Posted / mr.georgemathews
It is a common mistake to connect the lp side to the hp side
of the DPT and the Hp side to the Lp side of the DPT. SO we
need not to worry.
The solution is to remove the impulse connection from the
DPT , make a 180 degree turn of the diafram, which is the
connection mode of the DPT. If u see it you can see there
are holes on the opposite side also (H & L). which is just
the opposite to front side(L & H). SO no u can connect the
impulse line out here. And also we better recalibrate the
DPT Using HART Communicator.
This whole process will hardly take 5 min.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Where is wet leg is used?
kindly sent some demo question and answer
what is piezoelectric transducer?give an example in power plant n state its principle?
What are different types of cable?
please send data bank of quetions answers on analytical instrumentation.
hii my name is sujith...i am preparing for HPVL GET 2010... so ,,,pls help me by send any previous questions or material to my site.....(Msujith_12@in.com) thank q
For what reason would you possibly be compelled to make use of a Smith Predictor. Explain the idea behind the operation of this device.
If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?
Specific gravity.
WHAT IS TMXT IN TEMPERATURE FOUNDATION FIELDBUS.
what will the sending unit in the fuel gauge utilizes?
What is critcal speed. what is resonant frequency. why we want to cross crtcal speed on higher RPM (early).
How the sizing of the analog signal cable is calculate?
Basically iam Instruemntation Engineer, but Iam interested in Instruments design engineering, so plz guide, is there any course, training or Softwres to become Instrument design engineer??.
How to Calibrate Temperature Switch in field