How to calculate the Sizes of the cable required for one
specific load? Is there any formula for that? ( EX: For
400KW load,50mtr Length, What is the LT cable Size
required?)
Answer Posted / habeebm
Yes we have formula.....
Power P =400KW, Length L =50 Mtr, Voltage V =415V
ANSWER:-------
First find current,
Current I= 695.65A
Apply the factors in the below mentioned formula:-
R = pL/a
Where R=Resistance, p=Resistivity, L=Length, a=Area
Since p=12 for Aluminiun and 14 for Copper.
Then, R= pL/a
We know that V=IR
Apply "R" in Ohms Law
V = IR
V = I pL/a
Therefore ,
Area "a"= (IpL/V) / 1.732 (since 3 phase)
a = (695.65 x 12 x 50 / 415)/1.732
a = 580.69 ( Approximately 600 Sq.mm )
a = 600 ( 2 x 300 Sq.mm)
Therefore 2R, 3.5C X 300 Sq.mm cable is required.
Is This Answer Correct ? | 7 Yes | 2 No |
Post New Answer View All Answers
does a DG set has low fault level as compared to that of a transformer.If yes then why.
what is the purpose of bypass mode in energy lighting transformer?
how can i find cable size from current rating?
What is the difference between diode and a transistor in terms of the direction of current flow?
How is magnetic leakage reduced?
If Dg set load increase 25%, How much increase fuel Consumption (15 kva 2 cylinder DG set)
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm
From what on-site components does the HT panel monitoring the bus-bars in a 11kV system take inputs?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
what is Insulation monitoring device. where it is used? (in switchgear room or control panel or in field equipment)
Q.1:What protection will be used on HT and LT side of 33/0.4 KV, MVA transformer. Indicate capacities of protective device to be used. Q.2:Which types of back-up protections are used in the power transformers? What do you understand by the term over travel in the relay? Q.3:How star and delta connected winding transformer are provided from earth fault
actually i can't understand what is 3dB ? and it's really not clear to me.please any one let it me be cleared.
What do you mean by lighting transformer?
how to protect motor in dol starter having capacity of 30 hp.40 hp?
What is stepper motor?