I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.
Answer Posted / tauqeer hussain
We can use fromula for Voltage Drop Calculation
VD = mVxIxL/1000
VD = Voltage Drop
mV = Milli Volt(Given Rating Cable Manufacture)
Example 16sqmm mV =2.5 mv/a/m
I = Load Current
L = Lenght of Cable
Exapmle #
Voltage = 415vAC, Ampere = 25, Length of Cable = 100Meter
VD = 2.5x25x100/1000
= 6250/1000
= 6.25 (in volt)
= 1.50% (in percent)
Is This Answer Correct ? | 35 Yes | 8 No |
Post New Answer View All Answers
What is the necessary and sufficient condition for stability.
how to calculate magnetic force genrated by a coil ?
I meggared my 2c*70 sq mm AL AR XLPE cable. its one end show 50 M ohm . is my cable is safe for laying. I have only one phase and neutral.
How to identify the start and end of 3phase 12 lead motor if U1, U2, etc numberings are lost or erased.
Can we convert off line transformer to on line transformer
what you have to see after one week or month from the day of installation of transformer ?
ratings of lightning arrester
Why phase sequence must be same in any ht motor or generator circuit?if phase sequence doesn't same whatever will be affect on circuit?
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
What are the advantages of instrument transformer?
How many wall/floor flange will i use in bus duct system if we have in our design a 35th floor building.
ult of expression 'document.FrmQF.myem
What is the general system requirement of alternator?
The synchronous machine excitation system explain
how we can adjust for three phase motor cold stall time ,hot stall time and thermal register set up?