calculate multiplication factor of a trivector meter with
line ct ratio 200/5A, line PT ratio 11000/110V and meter CT
ratio 200/1A and meter pt Ratio 11000/110V.
Answer Posted / k.prakashchandra
If the line CT were of 200/1 ratio, the meter would read
correctly. As the ratio is 200/5, for 200 A primary current
the sec current will be 5 A instead of 1.0 .Hence you have
to divide the reading by 5 ,if it is capable of taking 5A.
Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
why we use sinosidal voltage / current instead of others in system?
hai...... tis is Hemanth. jst now completed electrical engineering... i wanna to apper for ap tranco exam... plzz send me the previous q's paper link......thanx in advance.
What are the special cables required for explosion proof wiring?
why current flow to the opposite direction of flow of electrons???????????
how to setting Load amps tripping time and extra settings for load Transformer protection relay with RMU panel using C&S model relay..?
Why the symbol of register is "zig zag"
State how to produce a constant rotating field by application of alternating currents to stator armature of a three-phase squirrel-cage induction motor
1. for eg, capacitor is used for many purposes(it act as filter, oscillator, bypass capacitor, memory storage etc...) 2. Please tell me some example circuits for different uses of capacitor( whenever and whereever and however we used capacitor as a filter, oscillator tuning etc..) 3. similarly for inductor and resistors(it act as what?) and when and how we want to act as like that?, and how we can used these components depends upon our requirments with example circuits and explanation? design to act as these components depends
what is the difference between directional & non directional earth fault with example please explain.
What is the need of generator relay panel
Q.1:What protection will be used on HT and LT side of 33/0.4 KV, MVA transformer. Indicate capacities of protective device to be used. Q.2:Which types of back-up protections are used in the power transformers? What do you understand by the term over travel in the relay? Q.3:How star and delta connected winding transformer are provided from earth fault
why ht cable end termination don't have a gland?
why i can not use thimble on capacitor duty contactor
No load tap changing transformer working
why the active power flow of some line is increased when the active power of out is cut ?