suppose in dcs range of a flow transmitter is 10t/hr what
is dp for 50% in 2500mmwc
Answer Posted / mithilesh kumar
tx range in dcs is 0-10 t/h.ok.
if ur TX showing 50% and 1250 mmwc then after square root
it is near 70% then in dcs ie that flow is 7 T/H.
if tx is showing 25% then this time mmwc will be 625.
after square root it is 50% and in dcs shows 5 T/H.
any comment u welcome
Is This Answer Correct ? | 9 Yes | 0 No |
Post New Answer View All Answers
How to calibrate the flow transmitter
Draw a simple circuit for a well head control panel used to protect the well against fire, leak, blockage, ESD, & controls the operation of one downhole & one surface safety valve. Explain the operation and controls
What is solenoid valve? Where it is used?
can we copy the software from a transmitter using hht(hart 275) ?
Galvanizing.
why using negative supply for bentley nevada vibration system ?
Can u tell me the principle of the tc,rtd,level switch,pressure switch ,transmitter(pr flow level temp.),vibration...plz
Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.
hi! i want to know about mpse exam.
How the warning lamp of a charging-system is activated ?
why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?
What is 3 element control system
, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.
need to calculate flow rate with the help of dp range and orifice bore dia and size. range is 0 to 400 inwc and orifice size is 12 inch 150 # rf and bore dia is 7.180 inch. need to calculation for flow rate
Why not come out analog output in ABB EL3020 when display show correct value