what is the effect of power factor to (a) voltage (b)
transformers (c) generators (d)transmission lines

Answer Posted / deepak thapa magar

On an AC power system, there are two kinds of power - real power (watts) that actually does work, and reactive power (vars) that enables transformers to transform, generators to generate, and motors to rotate. Reactive power doesn't actually do any work, but it must be produced, transformed, transmitted and delivered for the power system to perform its function.

So, power factor is merely a way of describing the relationship that exists between real power (P) and reactive power (Q), and the complex combination that is sometimes referred to as apparent power (S), measured in volt-amperes. Mathematically,
pf = cos (arc tan (Q/P)

Therefore, power factor has a maximum value of 1 when the power is all real, and a value of zero when the power is all reactive.

Now, you asked about the effect of power factor. That's a very broad subject. Here are a few very general statements:

- the flow of reactive power results in voltage drop. That is, the magnitude of voltage will be higher near the source of reactive power and lower near the reactive power 'load'
- it is harder to regulate voltage when power factor is lower than it is when power factor is higher.
- reactive power doesn't travel well, and it is generally preferable to try to produce reactive power as close to the point of consumption as possible.
- transmission lines are a source of reactive power. Transmission lines contain both series inductive effects and shunt capacitive effects. Therefore, a lightly loaded transmission line will produce more reactive power than it 'consumes' in transmitting power. There is a phenomenon called "Ferrante rise" in which the open circuit voltage at the end of a transmission line is higher than the voltage at the source end of the as a result of this capacitive effect.
- Generators have a power factor rating. Ultimately, there are three limits governing the capabilities of a generator. For actual lagging load power factors (that means vars out of the generator) above the rating up to the maximum value of 1, and for leading power factors (which means vars INTO the generator) from 1 down to some lower value, the generator doesn't really care about the power factor. In this region, generator capability is determined by thermal heating in the stator winding which is purely a matter of current. For lagging power factors below the power factor rating, power factor is important. In that region, generator capability is governed by heating of the field winding, and power factor is important it determining how much field winding current is required for a given stator output. Finally, for leading power factor operation, the capability of the generator is governed by heating in the end rings, and again power factor is important.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Help need in transformer !? Hello Friends The parameters of 2300/230 v 50hz t/f is R1=0.286 ohm R`2=0.319 ohm Rc=240 ohm X1=0.73 ohm X`2=0.73 ohm Xm=49.2 ohm Secondary Load impedance ZL=0.387+J0.29 solve the exact equivalent circuit with normal voltage across primery.. I know every thing but i cant find CURRENT I1=? and I`2=? Please help me give solution or only Formula please please...

2524


1.Z transform always lies around ? a) origin b) pole c) zero d) z=1. Multiples Mcqs which is bother me can’t find answers on internet. Some help required with little explanation . Note: this is not homework or related to any test. Thanks

1942


What are the basic component of a cro?

757


132/66kv sub-station procation ?

1719


1)we have 1000 cfm Blower,Dia-1Mtr,Velocity of air 94 m/s 2)We have Natural Air velocity 94m/s 3If i Put Wind Mill in natural air ,speed is 94m/s Then it will generate Assume 100kw 4)If i put same wind mill across the Blower,air speed is same 94m/s now the Question is Will it generate 100 kw?

1517






what is the difference b/w ground & virtual ground?

1848


Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?

1352


how withstand of hi-pot test outputs of transformer wire 2.5mm

1508


How will polarity test of Dy5 Transformer ?

1699


What is meant by reactance voltage?

631


I need the list of Universities who have summer intake for BS degree in Electrical Engineering.?

1564


What safety precaution are to be taken for avoiding electric hazards ?

1437


Tell me the reason of connecting domestic t/f primary in star or delta,and also secondary side.

1555


what are the standard IR values should be of R-E, Y-E, B-E, R-Y, Y-B, B-R of VCB in closed condition and in open condition for 500KVA & 1000KVA transformers. and what is the acceptable range when tested by 5000V megger.

1855


please write motor, transformer, Generator setting, fault level calculation of Tr.etc

1521