A pressure transmitter with a range of 0-100 bar.The
accuracy of the instrument is 1% of upper range value?
The pressure indicating transmitter is showing the system
pressure is 50 bar.
b. When you include the error, what is the minimum possible
pressure in our fuel gas system?
i. 49.5 bar
ii. 49 bar
iii. 1 bar
iv. 0.5 bar
We want to change the filter cartridge. We must depressure
the fuel gas system.
c. After we depressure the system in preparation for
maintenance, the transmitter displays a pressure of +0.1
bar. At this time, what is the possible range of pressures
in our fuel system?
i. +0.099 to +0.101 bar
ii. 0 to +0.2 bar
iii. -0.1 to +0.3 bar
iv. -0.9 to +1.1 bar
Answer Posted / waseem ahmad meer
For the first question, the answer is 49 bar.
For the second question, the answer is -0.9 to +1.1 bar.
Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?
How to calibrate level transmitter with use of HART?
What is wet leg condition and why is it used?
What is Positive Calibration and Negative Calibration?
What is loop1 and loop2 in MTS LT?
what is the difference between attemperator and desuperheater ?
How to find out the current of two motors having same power consumption but different RPM?
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
define feed forward control loop with example and drawing?
How we connect a instrument with ground, Give brief explanation with help of diagram?
the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)
what is actual drum level and compensated drum level?
How to calibration coriolis flow meter?
What is sensitivity in vibration probes..?
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....