hi frienda We have 750kva cater pillet dg set we are fasing
one diffrent proublam in dg we are start dg set after one
mint applying load around 450a load but dg was run 3 Or 4
mints after 3 mints dg was shuding down automatic how to
face this proublam pls tel any budy
Answer Posted / pillay
Can you determine why it is shutting down. is it a standby
genset, only works when there is a power cut and it operates
on its own. if it is one, maybe something is wrong in the
normal power present sensing circuit. when the DG runs it is
seeing as though the normal power is back so it should shut
down. or may be the stop signal is coming from the engine
asking it to stop.signals like low oil pressure over
temperature,over speed,
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How to size fuse? How to size MCB?
why there using acb enclosure in big buildings
what is destructive and non-destructive testing of welding
why in a swquence network representation, the negetive sequence generated voltage is taken as zero?
what is JE exam?
in basic 2 phase will short means tripping the power but spot welding 2 phase shorting but not tripping it will welded why.....(Q)
is there any lightning by passer is arranged in ship like buildings?
I have done my m.tech in electrical engg discipline. Can any one please suggest me how should I prepare for getting into phd in iit or nit.How should I prepare for getting into lecturership
why electronic instruments is more favorable than electrical?
What is essential to prove safe isolation of electrical circuit?
how to select correct size of power cable for inverter duty motor
in single phase converter, the no.of scr's conducting during overlap a)1 b)2 c)3 d)4
why +24 v and -48 v give to BTS? If -48v protect from surge then why we not use -24 v?
How generating electric power export to grid from the generating station ?
why the neutral point in connnection oscillates?