how to check a three phase induction motor by multimeter &
megger?
Answer Posted / will bg
Prove your meter/megger on a known resistance block. You
should remove any star or delta connection/bridges if at all
possible. If your earth/ground reference is not the motor
frame itself (i.e. a conductor in a cable) then first prove
your earth/ground by measuring on ohms the resistance
between your earth test point to various places on the motor
frame. You should get almost 0 ohms. Now measure your
phase resistances and they should always be fairly equal.
Rule of thumb is 10% variance. Remember the bigger the
motor the lower the resistance. Now on 500 volts DC measure
all phases to earth. Now switch megger to 1000V DC and
measure phase to phase resistance.
Is This Answer Correct ? | 6 Yes | 7 No |
Post New Answer View All Answers
a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------
what is the stear deltaprinceple?
what is basic difference betmeen normal & flame proof motor??
A 3 phase transformer's (Y-Y) Y and B phase is (Y and B connection not broken) broken from neutral and R and Nutral connection is ok, what will be the relay tripping and why
what is mean by D.O. in distribution line poles?
how can calculate 1kva generator running time in 1 liter keroscene
How many methods use the load flow solution?
WHY CBCT USE ONLY IN Y PHASE NOT OTHER PHASES
if a 3phase 100kva distribution transformer , 400 v,50 hz, 4-wire system is loaded at 160 k.w mostly 1-phase Lighting & Airconditioning split a.c load what will be the net effect on the power system in terms of voltage, powerfactor, current , efficiency of xformer
i have flexible wire. size of conductors is 0.190 mm & no.of conductors are 48. then size of wire comes 1.37 sqmm instead of 1.5 sqmm . the what is tolerance for this size.
What is fault clearing time for Current Limiting Moulded Case Circuit Breaker?.
what does a string of resistors in a series will do?
if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .
The loads are connected with phase and ground then why current flow as the loads ?
Show Details FROM:Muhammed Ikram TO:qa@allinterview.com Message flagged Saturday, June 4, 2011 10:07 PMMessage bodyHello all, i want to ask a question to all of you that what is VMM (voltage monitoring module )? how it work,s? i heard somewhere that it compare 1 phase voltage to other phase voltage. but there is also some setting on it. how to set it,s setting. please tell me briefly. Thank,s and Regard,s. Muhammed Ikram.