What are the maximum and minimum ratings of
MCB,MCCB,ACB,OCB,VCB and SF6 breakers?
Answer Posted / natha
International Standard IEC 60898-1 and European Standard EN 60898-1 define the rated current In of a circuit breaker for low voltage distribution applications as the current that the breaker is designed to carry continuously (at an ambient air temperature of 30 °C). The commonly-available preferred values for the rated current are 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A and 100 A[3] (Renard series, slightly modified to include current limit of British BS 1363 sockets). The circuit breaker is labeled with the rated current in amperes, but without the unit symbol "A". Instead, the ampere figure is preceded by a letter "B", "C" or "D" that indicates the instantaneous tripping current, that is the minimum value of current that causes the circuit-breaker to trip without intentional time delay (i.e., in less than 100 ms), expressed in terms of In:
Type Instantaneous tripping current
B above 3 In up to and including 5 In
C above 5 In up to and including 10 In
D above 10 In up to and including 20 In
K above 8 In up to and including 12 In
For the protection of loads that cause frequent short duration (approximately 400 ms to 2 s) current peaks in normal operation.
Z above 2 In up to and including 3 In for periods in the order of tens of seconds.
For the protection of loads such as semiconductor devices or measuring circuits using current transformers.
Is This Answer Correct ? | 8 Yes | 8 No |
Post New Answer View All Answers
Is any generator is developed which is operated with out diesal or other expensive source?
A cotter joint is generally used to transmit
What is meant by Im=30mA@Vk/2. How to know the kee point voltage for CT design
What is DC series motor?
WHAT IS ELECTRICAL MAINTAINTENCE ?
Is there any relevant technique to produce power from light and heat energy of the sun simultaneosly from same rays of light?
how to control dc motor?
what is the mechanical safety of DG ?
what is the function of statics switch in ups and tell me parts
Why the earth to phase voltage is high 250 compare to other two phases
Why line VTG = √3 phase VTG in star? How?
Could Please Explain briefly. Why used stabilizing resistance series with High impedance bus differential protection relay.
How to calculate KVA/VA rating of PT or CT from primary & secondary voltage or primary & secondary current?
The size and construction of bushings in a transformer depend upon?
What is mason's gain formula?