what is the function of anti-pumping in circuit breaker?
Answer Posted / mohamed elias
The anti-pumping relay is a device in circuit-breaker whose
function is to prevent multiple breaker closures. For
instance, if the operator gives the closing command to the
breaker by pressing the close button and the breaker
closes. However, a fault in the system causes the breaker
to trip. Since the close command is still in the pressed
condition, there is a chance of the breaker closing again
and being tripped by the relay multiple times. This can
damage the closing mechanism of the breaker. The anti-
pumping relay prevents this by ensuring that the breaker
closes only once for one close command from the control
panel.
| Is This Answer Correct ? | 14 Yes | 2 No |
Post New Answer View All Answers
wat is the current produced in a 5000v megger? when the positive and negetive terminals are touched on our body get s shock?
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm
Define cut-off rate?
I PURCHASED A DEISEL GENARATOR SET OF AVR TYPE& RATING 125KVA BUT SOME TIMES THE OUTPUT VOLTAGE IS FLUCTUATING WHAT ARE THE PROBABLE REASONS GIVE ME
What are dcs and plc?
i am venkat i got gre 930(verbal 270 quanta 660) and my toefl score 105..here question is why u got less score in gre ? what i supposed to tell...any chance of rejection is there...my accadamics record is very good
what & how to check the lightning arrester
While testing LA mast,What are the parameter limits ?
Dear all: Recently we got a question about Interface between PMS and SAP-PM.once we got a update message from PMS.we should set the deletional flag for functional location in SAP system.Is there any FM or BAPI to use?There are only functional location create and change provided by SAP. Best regards!
We are planning to synchronized DG's with our captive plant in the event of black start of plant, but before sync we checked voltage of DG with our plant voltage and it varies from 5 V to 450 V. So in this condition how we can sync DG with plant ?
What is the formula for selecting the cabels according to load? How to calculate what sq.mm cabel to be used?
The capacitive reactance of a capacitor of 1/(2(PI)) F at 10^3 H is
what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?
What is Phase margin?
What are the various types of rotor used in the alternators?