If Two Generators are working parellel in a network and
suddenly the field of one Generator get weakened What will
happened if there is no reverse power relay fixed in that
Generator panel????
Answer Posted / k.prakashchandra
Less excitation?. Then the generator will continue share the
load at leading power factor resulting in higher armature
current as the prime mover is still running and the terminal
voltage of the Gen is reduced.If this current exceeds the
set value ,Gen will trip on OCR which does not allow for
very low pf.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What are the essential characteristics of signal flow graphs?
Difference of induction motor & servo motor ??
In our plant we have installed new MCC with ELR and CBCT which is detecting some leakage current in the system but it leading to some confusion when to check that in which feeder which is drawing current we put off the whole panel itself but still CBCT detecting some leakage current so can anybody ans me , where i am going wrong or how to detect whether its actual leakage or CBCT malfunctioning.
How cable from Kit-Kat to main switch, from starter to motor are designed?
clarify types of motor operated valves and advantages
what type of questions are asked and howmwny questions belong this catagory?
What is the difference between diode and a transistor in terms of the direction of current flow?
what is difference between 5A and 100A CT constructional wise and operation?
In a flange coupling, the flange bolts are designed for
What is mean by hot and cold loop testing?
what happen if the parallel generator phase angle shift by 1 degree in manual mode
The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is
description with working of all parts of a Diesel generator???????
Draw the single line diagram of the power station?
Dear all: Recently we got a question about Interface between PMS and SAP-PM.once we got a update message from PMS.we should set the deletional flag for functional location in SAP system.Is there any FM or BAPI to use?There are only functional location create and change provided by SAP. Best regards!