1.what type of oil used in tranformer.
2.oil vesocity.
3.oil gauge.
4.witch time oil filterring & how much temperature
maintaned.
Answer Posted / pawar shyamkant sitaram
1] Minaral oil is used in the Transformer after filtration.
2] Oil viscosity is imprtant parameter to be watched while
transformer is in service.Normal practical value is between
21 to 27 CST.
3]Oil gauge is used to indicate the oil level in the
transformer.MoG is common gauge used in transformers main
tank coservator.
4]Generally temp. maintained at the time of oil filteration
is 65 to 75 deg.C.However it is to be decided by the
utility at what temp.fiteration is to be carried out.Oil
condition,Oil BDV & water containt in ppm are the main
factors for maintaining temperature while filtration.
Is This Answer Correct ? | 9 Yes | 0 No |
Post New Answer View All Answers
Why air circuit breaker off due to power failure?
what will happen reduce the transformer voltage from 415v to 406v, is it save the energy,? are this methodis good to reduce the energy.?
Is there any guideline say about display of earthing value near to earth pit
what is DRP panels?
what is the difference between fault current ant short circuit current?
What is the unit of charge and current?
State the types of distortions in amplifier?
As you achieve greater success with the company after some years, Will you like to be a share holder in our company?
What is the method of estamating of cable, CB,MCB ?
What is the approximate value of stacking factor?
explain working principle of earth leakage relay
If we are given a 10 amp cable type and asked to calculate the number of cores used and the thickness of the cable, how do we do it?? please help...urgent!! i hope the question is clear enough!!
how to test reverse power trip?
What is meant by stator? What is meant by rotor?
I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?