What is the minimum setting in REF relay because i am
facing some problem whenever power resumes after power
failure my transformer is tripping because of REF trip. I
am using CSPC make numerical relay(DIP switches). Now
setting is 15 percentage. What is the reason for this
triping. I sm waiting for answer
Answer Posted / k.prakashchandra
Your setting is 15% of In.While charging ,Tr draws initial
magnetizing current 6 to 15 times the In. Any difference in
measurements by CT s at this current ,may exceed the set
current.Even 1% error in measurement at normal current
becomes 15% of In at initial charging current at 15 times
the In
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
An active element is one which a. Supplies energy b. Absorbs energy c. Supplies energy and convert energy from one form to another
if an insulated power and control cables of a running gas diesel gensets laid direct in an open trench i.e, trench bed is not rcc of a power house in which rain water, spillage water alwas exists and all power control cables remains submerged even when gas gensets of 480 kw each runningin on load. These power &control cables runs from power house to switchgear room through these trenches in which water remains most of the time. pl explain its merit & de-merit
how to measure the current by compact digital equipment with dislay which fit inside any equipment
Instrument connected to a single phase supply
Where I can get the sample question for post of Junior engineer electrical-II For RRB Bhubaneswar.
WHTA IS LIMT OF LEAKGE CURRENT OF 11 KV 1 CORE 1000SQ.MM. XLPE CABLE.LOAD ON CABLE IS AROUND 600AMP .LENGTH 500 MTRS.
What is the tube exial fan?
How RTCC panel is working and give single line diagram for RTCC with transformer?
Explain about c.t?
What is the function of a neutral reactor.
explain with diagram how to protect transformers and substations from over current with help of CT's?
Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.
33kv substation lay out details & line to line & line to earth measurements
What is meant by Load Encroachment in OHL Feeder Protection?
aternator every parts and its working