We have a 1275KVA existing Transformer in a power plant
project. Customer want to get it test & confirm whether it
is a Dyn1 Transformer or not. Pleae let me know how to test
it.
Answer Posted / mani_mc2006
If they are mentioned or not leave it. Check the following
condition.
1)1U2n + 1W2n = 1U1W
2)1W2v=1W2w
3)1V2w > 1V2v
If it is satisfied with above. Then sure it's Dyn1
Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
what is the advantages og idmt relay over magnetic relay??
what is excitation/
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
Mention what are the types of semi-conductors?
What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2)
During regenerative breaking= A rotating magnetic field is reversed B slip is positive C torque is positive D slip is negative
Whats the difference btwn a latch, port,data bus buffer? Do they all not hold data in d flip flops??
what are the disadvantages in GIS over AIS
What can you contribute to the progress of our Company as an employee if you are selected?
bus bar design conditions and sizing pls tell me quickly
In DC generator, we use commutator, having no. of segments. Then how it is possible to get a half wave of voltage and current for half rotation of armature?
What is difference and reason b/w -48V BTS system and 24 V BTS system. Plzzzzzzzzz tel me.
What will be the effect of circulating current in HT xlpe cable when both the armour ends are grounded. Will the termination fils after some time in case of 33 kv supply.
Explain in brief description about the operation of DG sets.
how to find the Motor,s insulation Power?