what is the CT of protection and CT of metering ? what is
class 5P10 & 5P20 and class PS ?

Answer Posted / pin baloo

Standard accuracy classes:
At rated frequency and with rated burden connected, the amplitude error and phase error and composite error of a CT shall not exceed the values given in the following:
Accuracy class//Amplitude error at rated primary current(%)//Phase displacement at rated primary current(°)//
Composite error eC at rated accuracy limit primary current(%):

5P // ±1% // ±1° // 5%
10P // ±%3 // - // 10%
Marking: The accuracy class of a CT is written after the rated power. E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20
Accuracy limit current IAL:
Current transformers for protection must retain a reasonable accuracy up to the largest relevant fault current. Rated accuracy limit current is the value of primary current up to which the CT will comply with the requirements for composite error eC.
Accuracy limit factor kALF:
The ratio of the accuracy limit current to the rated primary current.
kALF = IAL/IN. (eq. 2)
The standard accuracy limit factors are 5, 10, 15, 20 and 30.
Marking: Accuracy limit factor is written after the accuracy class. E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20.

Is This Answer Correct ?    26 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit

1054


Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.

2295


How to address the servo drive for motor

1552


need to make a report. Need to choose a 3phase induction motor. Load conditions motor will operate in : Maximum Load: 30 Kw Speed: 2950 rpm Ambient temp: 20 cent Supply voltage: 440V Frequency: 50Hz need to look for the safety factor when choosing the motor, went through catalouge found a few, but dont know how to choose the safety factor allowing an extra load something above 30 KW to avoid any harm.

1313


why do we not use equivalent voltage source in negative sequence equivalent ckt.

1608






what is the role and fuction of automatic transfer switch in rotary ups

1443


As we use capacitior bank in 3ph ckt for improvement of PF, why not we use capacitor in single phase domestric use, at our house their are many inductive equipments,like fan,mixer,tube choke,air conditioner they also draw PF... by using capacitor can they improve PF. if yes--what are advantage and how to connect a capactor in single ph,and which type of capacitor if no- what are disadvantages.

1391


Can anyone tell the proper diagram of star delta starter????

1472


how the works electronic energy meter?

1668


In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..

1436


I'm looking for a softcopy manual set for a Credence ASL- 3000. Anyone know where I can get it?

1640


What are differences between Voltage, EMF & Potential difference ?

1401


we have amp, voltage, kw, length detail then how to calculte copper & alluminium size of conductor of 3-phase induction motor

960


Which device is used for the source of emission of electrons in a crt?

733


Why air circuit breaker off due to power failure?

712