what are the specifications for Dc cables of higher rating

Answer Posted / loboreliance2003

The DC voltage rating for high voltage insulation does not
take into account RF coupling of high voltage AC Signals
through the insulation to grounded objects. It is found
that high voltage wire insulation must be de-rated by
approx. a factor of four for the high voltage frequency
levels used. For instance, to run a 10KV triangle wave at
1KHZ requires insulation on the test cables with a DC
rating of at least 40KV.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to select circuit breakers rating eg. if i select a circuit breakers of capacity 40 amps DC with operating voltage 28 volts and if i what to use same circuit breakers for 300 Volts DC application what is the current rating of this circuit breakers.

1323


what are the reasons of CT circuit faulty in busbar protection scheme?

959


How to test Alternator stability test for REF relay

961


If a 3 phase induction motor is in off condition in the conveyor and rotor of the motor keeps moving with the conveyor than the resistance of windings of motor varies. why is it so ??

1562


What are the different power system losses and how can it be eliminated?

1573






what is apparent poewr, reactive power, & active power?

1734


State ohm’s law?

657


Define step response?

649


What happen when change order of CT in GIS feeder?

1185


Trafo ratio is 11kV/6.6kv,Vector group is YND11. What will be the effect if secondary is used for earthed system.

3352


i want to know that what is the eligibility critaria for ongc exam?

2569


can u give me a brief idea about power line carrier communication ??

1497


What is VSCF windelectrical system?

1351


I want to know Electrical Circuit?

1715


HOW TO CALCULATE HV CABLE SIZING?

2570