if in a level tx height is given, how u calculate the ranges
of the tx?
Answer Posted / s. kanniyappan
In case of Dry Leg
Span = (X)(Gl)
Hw at minimum level = (Z)(Gs)+(Y)(Gl)
Hw at maximum level = (Z)(Gs)+(X+Y)(Gl)
In case of Wet Leg
Span = (X)(Gl)
Hw at minimum level = (Y)(Gl)-(d)(Gs)
Hw at maximum level = (X+Y)(Gl)-(d)(Gs)
Gl=Specific gravity of tank liquid
Gs=Specific gravity of seal liquid
Hw=Equivalent head of Water
X=Max level
Y=Min level
Z=Distance b/w Datum and Transmitter.
Is This Answer Correct ? | 0 Yes | 2 No |
Post New Answer View All Answers
where proximity sensor installed on tank in loading arm application
how do u calibrate the vacuum transmitter if it shows more reading
Turbidity analyzer working principle ?
1. For Steam drum level signal, why do we compensate with drum pressure signal? 2.For main steam Flow signal is comensated with main steam temperature signal and main steam pressure signal why?
what is the input to be given in digital flow meter during the the calibration time?
what is your eligibility criteria for freashers?
Why does a pressure gauge installed on reactor, doesn't have any vent line below to release the pressure? Is it any kind of designing mistake or it actually does not require any vent line? And if it does not require any vent line below it then how we are gonna release the pressure built inside the pressure gauge?
what is RTV function in in process control?
how does we calibrate a square root flow transmitter ,give an example and explain it step by step like range calculation , calibration hook up series connection , zero check , and how to apply pressure , and if not geting proportional output then what should we do ?
what is SIL 1 2 3
I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?
Dear Friends, we are planning to design Power distribution and Fiber optic in the same cabinet.Like Front side Fiber optic and Rear side Power distribution.Is it any possibility of problem occurs like interference etc? Your answer is highly appreciate.
Can I calibrate the Electromagnetic Flow Meter on line and How.
which type of zones used for boiler? & why ?
How to calibrate the flow transmitter