oil sample dielectric test gives the insulation rupture
voltage at 26 kv. is this transformer safe to be operated .
The working voltage is 11 kv

Answer Posted / sms

AS PER IS:6792 , Oil Electric break down voltage( BDV) at
room temp using 2.5 mm gap should be Min 30 KV .
Accordingly don't take risk and carry out oil filteration
as early as possible to avoid any break down.

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

block diagram of 2 ups system connected in hot stand by mode?

7491


How would you calculate power loss in a resistor?

629


Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit

1052


What is the differentional relay...what is the work of this in power Tx. how it is works..

1447


how to copy from plc ge fanuc versamax series,all input and output, adress, and printout.

2048






How can I model an open-delta ground transformer for a network supplied by 4 unit GTG and power transformer in ETAP?

13291


what are the types of electromagnetic forces developed in practical transformer?

2169


What happens when ac supply is given as excitation voltage instead of dc supply

3137


How to back charge the Gas turbine generator

1618


we are having 110 Kv,250mA Electrostatic precipitators for coal fired boilers. what will be static voltage and current after discharge and what time it will remain before earthing?

1473


Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.

632


What is sink and source?

670


I have 4 busbar of 1000 ampere. we use 4 busbar to make 4000 ampere in one phase.my problem is that when we applied 60% load on that then busbar produced high noise.what is the reason of that and how can i minimize that noise.

1293


What is sensitivity of a measurement?

696


A 400 V, 50 Hz, Δ connected synchronous generator has a field reactance of 0.1 Ω and armature resistance of 0.015 Ω. At full load, the machine supplies 1200 A at 0.8 pf lagging. Under full-load conditions, the friction and windage losses are 40 KW and the core losses are 30 KW. What is the machine’s overall efficiency? Ignore any field circuit losses.

1337