Consider a level troll.
i am getting a correct value in 4mA and 20mA.
the value in the middle(30 to 60%)is disturbed and i am not
getting the appropriate value.
what is the solution to normalize the level and to get the
correct value..

Answer Posted / joe mccabe

a) calc the hyteresis and reset the 4-20 to it, accepting
the deviation in the middle

b) test the amount of deviation @ 4ma,8ma,12ma, 16ma,&20ma
and see if slope is repeatable, write program correction
for slope

c) Your instrument has a hardware issue, do the right thing
and replace it.

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.

1793


How will you test a transistor with a multimeter?

635


What is the difference between working pressure and calibration pressure of a control valve

2587


Why mmwc unit is used?

769


how u calibrate sox nox co2 co in cemps?what is opacity n HPm?tell the standard parameters of cems?

3202






What is the GK Value in Flowmeter?

3059


1.can you use SCADA instead of DCS,DCS instead SCADA 2.Difference between DCS and PLC,can their role be reversed i.e. role interchange 3.Difference between RTU and PLC

2081


What is the meaning of wet leg

679


How to work temperature gauge?

1406


Name different parts of a pressure gauge. Explain the use of hair spring in the pressure gauge.

674


i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?

1804


plz send me general of ongc

1547


What is zener diode? What is voltage regulator?

643


Identification of ss fittings, pilot valves, relief valve.

1393


how to calibrate 0- 150 psi presure gauge by dead weght tester

1496