Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Consider a level troll.
i am getting a correct value in 4mA and 20mA.
the value in the middle(30 to 60%)is disturbed and i am not
getting the appropriate value.
what is the solution to normalize the level and to get the
correct value..

Answer Posted / joe mccabe

a) calc the hyteresis and reset the 4-20 to it, accepting
the deviation in the middle

b) test the amount of deviation @ 4ma,8ma,12ma, 16ma,&20ma
and see if slope is repeatable, write program correction
for slope

c) Your instrument has a hardware issue, do the right thing
and replace it.

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?

1877


which type of filter gives the constant phase characteristics?

1927


what is the input to be given in digital flow meter during the the calibration time?

2241


how pressurize drum calibrated ?

2059


What is voltage regulator?

1111


what is droop in governer ,type of droop ,how it work

2160


what is the vital subject for scoring bhel exam&what is the question pattern

2424


How to convert mmWc(mili meter water colam) to tph(ton per hour)?

1000


Meaning of the following a. IOP- Manimum; b. IOP- Maximu,;

2191


What is the difference between uv and ir scanners? and what is the workig principle of both

2380


can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?

4735


please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com

1689


why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.

2741


while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?

2219


What is standard procedure of manual mapping in Radar type level transmitter?

1955