What are the difference between C-Curve and D-Curve for
MCB's.

Answer Posted / nimda

The magnetic trip for a B-curve MCB will not operate below 5
times rated thermal current but will surely operate
instantaneously above 10 times rated thermal current.
The magnetic trip for a D-curve MCB is will not operate
below 10 times rated thermal current but will surely operate
instantaneously above 20 times rated thermal current.
The choice between B-curve and C-curve depends on the loads
ratio between load inrush current and load running steady
state current.
For the same running load current if the cable is long then
a D-type MCB may need a larger cable cross sectional area,
compared to a C-type MCB, just to ensure that sufficient
fault current always is available for operation of the
instantaneous magnetic trip.

Is This Answer Correct ?    31 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

define reflection method?

1498


what is the write prosidure of stringing of 8meter pcc pole.

1980


what is doid

2308


Define availability (operational)?

663


Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.

1743






can any one suggest paper presentation topies for electrical engg?

1505


why we permissive overreach in distance protection.where it is applicable to use in long r short lines

2296


Why synchronous motor is used in power factor improvement,dc series in lift

1192


What is power distribution criteria for converting single phase unbalanced residential load to 3 phase star connected balance system. Does total KW converted to 3 Phase. Means Divided by root 3.

1845


How to calculate capacitor bank value to maintain unity power factor with some suitable example?

673


can u give me a brief idea about power line carrier communication ??

1497


Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.

1563


in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer 

1296


explain single phase series motor

1457


What is control system?

728