dear all, in motor operation , motor is of 100 hp and
bimetal relay setting is 130 amp, if relay is getting
tripped on 120 amp balance current what can be the
reason? Relay is newly replaced. I dont know but is
there any frequency effect in thit case? Can frequency
variation affect bimetal relay operation?
Answer Posted / k.prakashchandra
Bimetallic relays are not very accurate.Ambient temp also
plays a role for setting as the relay acts at a certain
temp.Hence you have to compensate for ambient
temp.Frequency has no effect on the setting .
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Apparent power is expressed as V * I(Conjugate). Why not in V * I ?
if 6 earth pit value is 1.5 ohm then what should be the number of earth pit to make the value .8 ohm
The synchronous machine excitation system explain
how the speed of the gets motor regulated. does it draw the same current on the all speed level.
What is voltage ratio of a transformer?
in science exhibition how lamp can blink when you clap near the lamp ? thank you
why r we using shell transformer for low voltage
is it possible to test of bus bar in high rise building without completed full floor ?
What are chief characteristics of state-space method and its techniques ?
in india per day how much power is generated including all power station
with 3 phase board on a 63 amp rcd is it ok to have 6 electrical showers 2 on each phase and what problems could happen
WHAT IS AIR GAP VALUE IN MM FOR A 11KV BUSHING OF 11KV/440V DISTRIBUTION TRANSFORMER. AND AIR GAP VALUE OF 25 KV BUSHING OF AT TRANSFORMER OF 25 KV TRACTION. WHAT IS THE CALCULATION FOR THE AIR GAP PERMITTED FOR BUSHINGS AT DIFFERENT VOLTAGES.
How to select the earthing transformer,for DELTA TO DELTA TRANSFORMER OR ALTERNATOR SIDE.Pls post your answers and calculation.
What is dc current source? Differentiate between ideal and non ideal current sources?
if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .