What is the major difference between P.T. & C.V.T ? Why CVT
is used in HT Transmission line in place of P.T.?

Answer Posted / zeeshan

Well PTs and CVTs are both used primarily to measure voltage.
Primarily is used coz in CVT, we use it for another equally important aspect , i.e. to filter out the PLCC carrier wave.
AS regarding what's PLCC, thats a diff. concept altogether, and doesnt need a mention here.
PT and CVT both can be used both for 11KV and above lyns...but in practicality for 132KV and above....the transformer w/g of PT becomes highly bulky...and hence losses are more.
Whereas in CVT instead of the usual "Transformer w/g" we use as already said...capacitor series...thats performs two notable functions:
1) gives a low impedance path to PLCC carrier wave freq. which is of order of 100-500KHZ...and hence its used for protection and relaying and telemtering purposes
2) it is as already said...the voltage drops across each cap. and hence its viable to measure the voltage by using low coiled transformer...

So both PT and CVT can be used for any lyn...that be 11KV or 220KV....but as the line voltage increases...the losses in PT increases...and CVT provides that other extremely imprtant function. which PT totally lacks.
So in terms of economy and advancement CVT have been steadily replacing PTs as CVTs rank much higher in terms of efficiency , usability, and longevity

Is This Answer Correct ?    67 Yes 12 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The electrical energy required to raise the tempreture of a given amount water is 200 kwh. If the heat losses are 20%, the energy required is?

1519


What are the advantages and disadvantages of negative feed back?

643


What should be the values of settling time, peak time, steady state error, overshoot, rise time, MPOS (Maximum percent over shoot) to keep the system in transient state, to keep the system in steady state ?

1765


how was your last weekend.

1340


im electrical engineer, could any one help me for FEWA exam questions please ?

567






why is the conservator tank painted white on the transformer

2570


Why an ac systems are preferred over dc systems?

639


Ratings of power transformer,Distribution transformer.

1101


How 48-relay (incomplete sequence) functions?

3551


what is the difference between gas group b and gas group c electrical equipment construction wise?

1391


Write the force balance equation of ideal spring element.

782


What is dielectric loss?

649


how can i change the rotation of the AC single phase induction motor and show me by diagram

1316


We are preparing another project which involves Waste heat recovery from a 1 MW GE Engine. The Engine in particular gives out flue gas at 487Deg C with a flow rate of 5650 kg/hour and this can be cooled to 180 Deg C. This gives a thermal output of ~ 594 KW that is available for input to VAM via heat exchanger / boiler. Additionally 581 KW will be available from engine jacket water (temperature profile 80/ 80 Deg C and a flow rate of 50m3/hr) Our estimation is that 300 TR of cooling is possible with a suitable VAM machine(s). Please advise what is the most suitable arrangement with maximum TR and min Capital expenditure. plz reply me as early as possible

1504


Under wat condition statcom operates as an inductor for the transmission line?

1430