what is the role of impedance in transformer?based on
secondary f.l.current(139 amps) and impedance(4.07) of
415/415v of 100 kva transformer. what is the primary
current?
Answer Posted / ma.amulraaj,b.e. mba.,
It is %impedance Voltage.In Transformer,%impedance Voltage plays significant role .Here 100KVA,11KV /415 V.
Full load current Sec .current= VA / 1.732x V (Sec.Voltage)
=(100x 1000 )/(1.732x415 ) =139 Amps, ok
Full load current Primary .current= VA / 1.732x V (Primary
Voltage)
=(100 x 1000)/(1.732 x 11000)
=5.25 Amps
Here ,the full load secondary current is 139 Amps,the rated secondary voltage is 415 V,we can do Short circuit test by applying secondary voltage 415 V,we cannot get the full load secondary current,due to impedance of Transformer.Then we have to raise the secondary voltage gradually, at particular voltage it delivered the full load secondary current,note down the voltage say 440V.From that voltage we have to find out % impedance.440 /11000 = 4% %Z=4.0 %.As this case %Z=4.07,ie. it is (4.07 x11000)/100 =447.7 V.It means This transformer may delivered a full load current at 447V.
This % Impedance may vary from Transformer to Transformer.
Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
how calculated Transformer losses.
state basic meaning of 'INDUSTIAL AUTOMATION'?
how braking & making capacity of circuit breaker are calculated?
previous year paper of ntpc bhel for degree in electrical enng
difference between main metering kiosk and check metering kiosk
WHY NUTRAL GROUND SYSTEM USED IN 33KV SYSTEM
What are the symptoms of a bad PG card of a drive (inverter) esp. of Yaskawa Ac Drives (inverters) G7 ?
bus bar design conditions and sizing pls tell me quickly
What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?
why +24 v and -48 v give to BTS? If -48v protect from surge then why we not use -24 v?
Hi,iam a diploma in electrical engineering.rtd from indian air force in apr 2007.prsently working in reliance next link as a network maintenance engineer since 2007,can i get a job in motherson sumi.
can you any one give exact mathematical relation between AC current and DC current?
What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?
what is mean by restructuring power system?
How to know about the rating(voltage and other) of induction motor if its name plate is missing at the manufacturing site.