What is the difference between earthed & unearthed system?
Answer Posted / meenakshi
By Earthed system, we mean a three phase system whose star
point is grounded directly. In this case, in the event of
the earth fault, the voltage in the faulty phase will
become zero. The voltage between the healthy phases and the
ground will be the same, 11kV/1.732 or 6.6/1.732.
However, in case of an earth fault in an ungrounded system,
the voltage between the healthy phases and the ground will
be equal to the phase to phase voltage. i.e. 11kV or 6.6 kV.
Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
What should be the magnetic balance test values for a 3 phase delta/star connected single primary dual secondary winding transformer (90 MVA / 2 X 45 MVA TRANSFORMER)
diff.between servo motor and ac motor
What is meant by derating factor?
bsec exam syllabus (mis)
sir, i am 3 years diploma course pass out candidate.what type of certificate can i got in marine service.
my question is how to answer the question "you are from b.tech eee background and why do you want to go for banking
harmonics filter
In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.
i've iocl interview.. if you know the interview process please give me information..
what is meant by 2 within a star in a voltmeter dial?
what is the pulse and audio frequency transformer? what is different between induction regulators and tap changing transformer?
what is high and low cut off voltage of BB and DG at SPS????????
What types domain of laplace transforms? What behavior can laplace transform predict how the system work?
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
Is there any question in the name of Static Switch in UPS??