what is the significance of KV & MVA rating of the
transformer and how they are related.
Answer Posted / eduardo
kV means kilo Volts, and is 1000 V. So 10kV means 10 000V.
This is the operating voltage. You must have another voltage
in the transformer. One is for the primary, and the other
for the secondary.
MVA means Mega Volt Ampere and is the power of the transformer.
1 MVA = 1 000 000 VA.
For example. If you have a transformer 10kV/400V and with 1
MVA, this means that at full charge is able to delivery in
the secodanry 1 000 000 VA / 400 V = 2 500 A.
He must be connect at a power line 10 kV and will delivery
400 V (till the load of the seconary reach 2 500A, after
that the value of the tension in the secondary begins to
drop, but this is another story).
In the primary the current will be 1 000 000 VA / 10 000 V =
100 A (at full charge).
| Is This Answer Correct ? | 25 Yes | 24 No |
Post New Answer View All Answers
How to select circuit breakers rating eg. if i select a circuit breakers of capacity 40 amps DC with operating voltage 28 volts and if i what to use same circuit breakers for 300 Volts DC application what is the current rating of this circuit breakers.
What is effect on in zone and out zone fault if CT chosen for phase side is Vk/2<5mA and Neutral side is Vk/2<15mA on REF protection of Transformer
Is neutral transformer can be called as control transformer?
Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?
how calculate gd2 of ht motors
what is excitation/
I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.
how is calculated the quantity of weight in hot test xlpe?
explain me the relation between torque, frequency,speed,voltage and current in the 3 phase induction motor?
upto how much low RPM we will run the commercial motor which is run through VFD without any problem occurs in motor.Motor rating Duty is S1 & RPM is 1400.
hi can anyone pls tell me the eee interview core questions asked in l&t
why co incidence factor considered in transformer sizing?
What consists of 2 or more thermocouples to be connented series?
Which type of questions well asked. ?
How you will determine the volume of oil in a particular Distribution transformer.