how to calculate the input current in singel phase and
3phase supply to 5kva ups

Answer Posted / h s dhillon

Let the supply is 3 ph 4 w having line voltage 400 volts
and phase voltage 230 volts,then:
in case of single phase:
I=5000/230=21.74 Amp
In case of 3 phase:
I=5000/Under root3 i.e.1.732x400
=7.22 Amp

Is This Answer Correct ?    7 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

when the Transmission and Distribution network where is the "feeder" lines are located? and why should be used in T&D network.....

1258


Describe Non I.S. Earth System and why is it used?

1292


Diagram and details of polarity test for Current Transformer 11kv 400/200/100/1A

2566


How cmd is calculated in case of energy neters

1380


How to calculate ant test the burden of Current transformer

1953






Is it possible to operate a synchronous 2-poles turbogenerator with a still-in-place faulted bar but electrically disconnected ???? If yes, should I act on the other phases as well ???

1446


Why mostly the HV side of transformer has Delta?

2757


What happened when capacitor connect series in ac circuit?

968


i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.

1781


can i connect the two phases of scott connected transformer,if not why?

1511


why would the rotor rotate at sub synchronous speed against the direction of rotating flux when d rotor of 3 phase IM is connected to 3 phase balanced supply and the stator windings are shortcircuited ??

1530


Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit

1052


A generating system will have a total capacity of 300 MW. Find the probable forced outage when the capacity is supplied by two 150 MW units. The operating probability of all units is P=0.98 and forced outage probability rate Q =0.02 .

2141


What is the disadvantage in proportional controller?

630


What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.

1812