how to calculate the input current in singel phase and
3phase supply to 5kva ups
Answer Posted / h s dhillon
Let the supply is 3 ph 4 w having line voltage 400 volts
and phase voltage 230 volts,then:
in case of single phase:
I=5000/230=21.74 Amp
In case of 3 phase:
I=5000/Under root3 i.e.1.732x400
=7.22 Amp
Is This Answer Correct ? | 7 Yes | 2 No |
Post New Answer View All Answers
when the Transmission and Distribution network where is the "feeder" lines are located? and why should be used in T&D network.....
Describe Non I.S. Earth System and why is it used?
Diagram and details of polarity test for Current Transformer 11kv 400/200/100/1A
How cmd is calculated in case of energy neters
How to calculate ant test the burden of Current transformer
Is it possible to operate a synchronous 2-poles turbogenerator with a still-in-place faulted bar but electrically disconnected ???? If yes, should I act on the other phases as well ???
Why mostly the HV side of transformer has Delta?
What happened when capacitor connect series in ac circuit?
i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.
can i connect the two phases of scott connected transformer,if not why?
why would the rotor rotate at sub synchronous speed against the direction of rotating flux when d rotor of 3 phase IM is connected to 3 phase balanced supply and the stator windings are shortcircuited ??
Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit
A generating system will have a total capacity of 300 MW. Find the probable forced outage when the capacity is supplied by two 150 MW units. The operating probability of all units is P=0.98 and forced outage probability rate Q =0.02 .
What is the disadvantage in proportional controller?
What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.