what current is taken from a double wound 500kva transformer
Answer Posted / bala
hai
DATA
Tr rating = 500 kva
voltage rating = 415 v
Calculation
500 / rt 3 x .415 0r
500 x 1000 / rt 3 x415 = 695 A
i hope now u are clear
Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
we have require a Motor (1500kW, 6.6kV, 50Hz) which shall operate at 1500rpm during 30min and after it shall run on 500rpm during 15min. The same cycle shall be repetitive during the whole working days. Which method is best and economic to achieve such type of task. VFD, VVFD, Pole changing motor etc.