how to calculate knee point voltage of current transformer?
Answer Posted / arvind negi
CT Knee Point Voltage Calculation Sheet
Primary Secondary Volt
Resistance Resistance Length
In MVA In AMP In kV In ohm In
ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection -
1200 1 - - - - -
2 Transformer Rating, MVA 20 - - -
- - - -
3 % Impedance, %Z - - - -
- - - 13.9
4 Voltage of Line Side, KVLV - - -
11 - - - -
5 CT Secondary Resistance, RCT (ohm) - -
- - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm.
- 8.5 -
7 Loop Length of Control Cable - - -
- - - 120
Calculation:
1) Fault Current at Primary Side of CT (kA) =
MVA/*100(%Z*1.732*KLV) 7.55
2) Fault Current at Secondary Side of CT, If (A)=
6.29
3) Cable Lead Resistance, RL (Ohm)=
1.02
4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)
101.2
REMARKS : -
Knee Point Voltage of CT provided by CGL for REF CT
= 115V and for Differental CT = 200V are in order.
| Is This Answer Correct ? | 8 Yes | 4 No |
Post New Answer View All Answers
Is there any specialised book to refer about fault level calculation both in MV and LV side??
When can we take Neutral as common neutral link?
Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?
How to calculate the input cable rating for 10kva ups (3phase input and single phase output and also 3phase output, battery rating 65Ah)provide the formula also.thnx
The magnitude of sum of two sinusoidal av voltage is equal to 230 volt.the magnitude of each individual voltage is also equal to 230 volt.what must be the phase difference between voltages?
orifice sizing how done, checking & selection
Between educational qualification and practical work experience, give us a brief explanation on your practical experience in your past Endeavour that you performed well to the satisfaction of your past or present employer?
I have a 380 KVA DG set. How can i find out 1. My Fuel Consumption per hr ? 2. Electricity produced in 1 Hr. ? 3. If load varies then how does it affect fuel consumption & electricity produced ? Please HELP !!! Really need an answer.
i want to learn control schedule for 11kv panel? can any one send the detailed control schedule?
Lt motor sfu flashing reasons?
what is the affect of earth's magnetic field on the frequency used in aircraft???
Which device of PlC does share load between DG sets when DG are running in perallel?
Can anybody tell abt concrete encased earthing or grounding?
HOW TO CALCULATE THE HEAT AND LOAD OF LT-SUBSTATION WHICH CONTAINS 2*1MVA TRANSFORMERS,LT SWITCH BOARD,MLDB,ACB,BUSBAR,ETC...?
Why the output of OP-AMP is always less than Vcc?