how to calculate knee point voltage of current transformer?
Answer Posted / arvind negi
CT Knee Point Voltage Calculation Sheet
Primary Secondary Volt
Resistance Resistance Length
In MVA In AMP In kV In ohm In
ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection -
1200 1 - - - - -
2 Transformer Rating, MVA 20 - - -
- - - -
3 % Impedance, %Z - - - -
- - - 13.9
4 Voltage of Line Side, KVLV - - -
11 - - - -
5 CT Secondary Resistance, RCT (ohm) - -
- - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm.
- 8.5 -
7 Loop Length of Control Cable - - -
- - - 120
Calculation:
1) Fault Current at Primary Side of CT (kA) =
MVA/*100(%Z*1.732*KLV) 7.55
2) Fault Current at Secondary Side of CT, If (A)=
6.29
3) Cable Lead Resistance, RL (Ohm)=
1.02
4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)
101.2
REMARKS : -
Knee Point Voltage of CT provided by CGL for REF CT
= 115V and for Differental CT = 200V are in order.
Is This Answer Correct ? | 8 Yes | 4 No |
Post New Answer View All Answers
Explain advantages of storage batteries
what is draiv work
while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends
what is the calculation formula for motor starting torque,running torque, running torque.
battery capacity use of made?
Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??
while starting a liquid starter ,is there any volage drop on water/soda on tank.can we touch the tank on starting?
The moisture in air will condense at
if a.c supply is given to the motor,, what happen?
I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.
WHAT IS counter flux IN CT?
what is deffrence between squirral cage and wound rotor in IM?
1.why we are using metal oxide gapless block in lightning arrester,2.What is minimum and maximum rating of metal oxide blocks using in india
what is mathed of check the D.C MOTOR 181 KW (ARMATURE AND FIELD) WHAT IS THE MATHED OF CHECK THE THYRISTOR MODULE (HIGH CURRENT)
what are the differant std sizes of cable trenches?