how to calculate knee point voltage of current transformer?

Answer Posted / arvind negi

CT Knee Point Voltage Calculation Sheet



Primary Secondary Volt
Resistance Resistance Length
In MVA In AMP In kV In ohm In
ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection -
1200 1 - - - - -
2 Transformer Rating, MVA 20 - - -
- - - -
3 % Impedance, %Z - - - -
- - - 13.9
4 Voltage of Line Side, KVLV - - -
11 - - - -
5 CT Secondary Resistance, RCT (ohm) - -
- - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm.
- 8.5 -
7 Loop Length of Control Cable - - -
- - - 120


Calculation:

1) Fault Current at Primary Side of CT (kA) =
MVA/*100(%Z*1.732*KLV) 7.55

2) Fault Current at Secondary Side of CT, If (A)=
6.29

3) Cable Lead Resistance, RL (Ohm)=
1.02


4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)
101.2




REMARKS : -

Knee Point Voltage of CT provided by CGL for REF CT
= 115V and for Differental CT = 200V are in order.

Is This Answer Correct ?    8 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain advantages of storage batteries

652


what is draiv work

1449


while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends

2374


what is the calculation formula for motor starting torque,running torque, running torque.

1226


battery capacity use of made?

2105






Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??

2939


while starting a liquid starter ,is there any volage drop on water/soda on tank.can we touch the tank on starting?

1448


The moisture in air will condense at

682


if a.c supply is given to the motor,, what happen?

1687


I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.

980


WHAT IS counter flux IN CT?

1530


what is deffrence between squirral cage and wound rotor in IM?

1538


1.why we are using metal oxide gapless block in lightning arrester,2.What is minimum and maximum rating of metal oxide blocks using in india

1520


what is mathed of check the D.C MOTOR 181 KW (ARMATURE AND FIELD) WHAT IS THE MATHED OF CHECK THE THYRISTOR MODULE (HIGH CURRENT)

1563


what are the differant std sizes of cable trenches?

1534