how many test is necessary for 27mva transformer.
Answer Posted / satya dev
Basicaly Transformers having two type of tests 1-
Manufacturing & 2- Field test, Manufacturing test are
described Above & Field tests are carried out during the
Commissioning at site.Field tests are given belwo..
Insulation Resistance Test- Phase to Phase, Phase to Earth,
Winding Resistacne Test.
Testing & setting of WTI & OTI.
Vector Group Testing.
Magnetinc Ballance Test
Ratio Test.
Knee Point Test.
Tan Delta Test ( This is Also IR test)
Hi Voltage Impulse Test (if Client requested)
etc...
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing
Can clean earth cable be considered as low current cable
what is PDU in transformer?? which company manufacture??
Electrical Engineering
In TNC switch, is there any 1NO+1NC block ? and if we move over closing position, is ther any affect on trip position or vice versa?
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
What is lc oscillator?
What are the three types of compensators?
What is the tension required for the 25000 CFM AHU belt
1.Can we use 6.6/11KV 300sq mm xlpe 3core cable for LT use (415 Volt). 2. If we use it for LT then what is the current rating
Differentiate between kirchhoff’s first law and kirchhoff’s second law?
If rotor works in clock wise what happens
What is the requirement of grounding the neutral of single phase generators on load? If the neutral is not grounded, what will be the effect?
can anybody send the rrb chennai &rrb bopal question papers of 2006&2007.My exam is on 12 oct 2008.Its urgent
why would the rotor rotate at sub synchronous speed against the direction of rotating flux when d rotor of 3 phase IM is connected to 3 phase balanced supply and the stator windings are shortcircuited ??