Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is the difference between sensitive earth fault and
restricted earth fault in power transformers?

Answer Posted / raghavendran

Sensitive Earth fault protection: Normally used on systems
where the earth fault current is limited to a very low
value. Scheme consists out of a ring CT (Core Balance CT)
around the three phase conductors, and the relay connected
to the secondary side of the CT. A very low setting is
possible, even sometimes lower then 1% FLA. Need to
coordinate with similar relays downstream. This method is
based on primary current vector addition or flux summation.
The conductor
cables pass through the center hole of the core balance CT.
Secondary current is the system zero-sequence current
3I_0.This scheme provides increased sensitivity with no
false residual currents. However,
care must be taken to prevent false tripping from unbalanced
inrush currents that may
saturate the current transformer core.

residual Earth Fault Relay:Restricted Earth Fault Protection
Is a type of zone of protection, or a differential scheme.
You get two types, low impedance and high impedance. Low
impedance is normally current operated and high impedance
voltage operated. High impedance REF is the most commonly
used. Relay connected in parallel with three phase CTs and
one neutral CT. It will look just for faults inside the
transformer, and need not to coordinate with relays
downstream (can operate very fast). With this kind of
protection you can protect over 90% transformer windings.
Need to use special class CTs, previously called class X
CTs.low impedance REF, are incorporated into some the new
microprocessor relays.

Is This Answer Correct ?    42 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?

1823


Enlist four components of electrive drives.

1850


How is magnetic leakage reduced?

1184


Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir

1947


what are all types of cross section in AC cables?

2313


What is pi controller?

1196


could you measure current in parallel?

1120


prove that power consumed in 3 phase delta system is 3 times as compared to 3 phase star system

2293


why is the power generator connected as star earthed or star earthed through reactance and what its features ?

1694


what is relation between ct and pt ratio with multiplication factor of a energy meter? is there any other factor on which multification factor depend?

2351


How to calculate multiplying factor of dc energy meter

1678


What is the instrument to check the rotating diode fuse of alternator in running conditions?

2482


what is subtransient , transient and steady stateac components

2178


How o select the electrical fuse?.What are its characteristics.How to select the material od fuse?

1994


WHAT IS THE MEANING OF BALANCED / UNBALANCED IN STABILIZER TYPES.

2672