how to check the stabilty test for generator differential
protection
Answer Posted / raghavendran
Checking of the pickup and dropout value
When checking the pickup value, the analogue input signals
of the single phase alternating test current have to be fed
to the relay via terminals.When testing the pickup value,
the alternating test current must first be lower than the
set pickup value.
Then the current will be increased until the relay picks up.
The value that can be read from the ammeter may not deviate
by more than ± 2.5% of the setting value. The tripping
values for the other current inputs should be checked
accordingly.
Function test
Disconnect all leads for adjusting the interposing C.T.s and
perform the following function test:
Load the generator with minimum 50% load. Assure that the
tripping of the generator C.B. does not cause un-wanted
damages (blackout).
To operate the differential relay use a shorting link
between one of the phase measuring sockets
and GND, e.g. connect Line to GND. The relay should trip
immediately. If no trip occurs, make sure
that the load current exceeds the set value.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?
why is the conservator tank painted white on the transformer
what is the working principle of a DG Set, Alternator, & exiter
what is stper motor
# 4 hi friends i m from electrical branch and seeking for tech. + apti. both papers of hpcl plz get it available as soon as possible my email id is sumit_lig189@yahoo.co.in
what is the minimum (Common factor) insulatin resistance of the following a, 4mm sq wire b, cable from 50 mm sq to 800mm sq
What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?
xpression 'document.FrmQF.myemail' [
Motor,transformers,capacitor tubelight etc....
1.what is mean by 8/20 micro sec waveshape
how to measure earth resistance of a substation
Does outdoor isolator loose connection cause short circuit current in that circuit? if yes then how ??
is it necessary to earth the rmu before cutting off the transformer winding?if yes why?
the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?
How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?