what is ceiling voltage in an exciter?
Answer Posted / raghavendran
Consider a Generator operating in three different conditions
when operating at rated load,the AVR applies rated DC
excitation to the field.But consider a condition when there
is a sudden load throw off, the terminal voltage at the
stator will be increased.To compensate for the sudden
increase in voltage level, the DC Exc is reduced
drastically.This is called as 'Negative Ceiling Voltage'.
But when there is a sudden increase in load the terminal
stator voltage drops due to external reaction effect.Hence
the drop in terminal voltage is compensated by sudden
increase in DC Exc.This is called as 'Positive Ceiling
Voltage'.For this the response time of the AVR has to be quick.
The minimum and maximum ceiling voltages may range upto 1.5
times the DC Exc voltage at No-Load and Full Load respectively.
Is This Answer Correct ? | 48 Yes | 4 No |
Post New Answer View All Answers
In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????
Post possible questions for Power Factor Panel FAT / SAT
Why lose 1 phase voltage in 33kv to 415v stepdown transformer
What is the general power factor & min. power rating of TV,LCD type TV, CRt type TV, Scanner, printer?
formula for calculation of switchgears(i.e. contactor, fuse, cb, relay etc.), if load current is given?
bus bar design conditions and sizing pls tell me quickly
What effect does a very low impedance have on the Voltage regulation? On the short-circuit current?
why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?
How to calculate capacitor bank value to maintain unity power factor with some suitable example?
how to avoid Saturation in C.T?
it is possible to measurement of tension of slipring induction motor(SRIM)carbon brushes, any maesuring instruments are available in the markets.
Why we specify TNC switch with 1NO 1NC ,2NO 2NC ? how we get connection.?
How To increase Knowledge Of boliler regarding To Only Electrical Field..
Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.
I have made a 3 phase thyristor full bridge rectifier. But at the moment it is working only for the half bridge operation. Both the half bridges are on operation separately but when i put it into full bridge operation the oscilloscope output is zero. I rechecked that the pulses are correct for each thyristor. what could be the possible reason for this?