when current lags behind voltage how does it affect the
circuit.In other words what is the significance of lagging
current?

Answer Posted / karl

I dont think the significance is that you will lose energy.
For example if I was to connect a capacitor in a AC
circuit, it would charge and then discharge back into the
supply. Therefore not using any real power. This would be
the same for a pure coil with its reactive energy. I think
the problem with a poor PF is that for a certain load you
may need to have a bigger transformer or generator. For
example a 1kW load with PF if 0.5 would need a xformer size
of 2kVA. If the PF was 1 you would need only a 1kVA
xtransofrmer even though you are still using the same power
and therefore energy.

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain what is electric traction?

656


A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N

2122


ACCORDING TO IEC WHAT SHOULD BE THE MINIMUM HEIGHT OF G.I. STRUCTURE OF CT, PT, ISOLATOR, LA?

1617


a battery is having capacity 100AH and 25% charging .if a load taking 10A & connected 6 hour .what is the final condition of the battery.

1195


How can i calculate the Breaking capacity of molded case circuit breaker, is the breaking capacity of CB for Diesel generator shall be less than grid supply's breaker ?

1704






How to check the Bushings of the transformer?

1263


11000volt DG set carnt kaise banvay

1228


send me all basic electrical question and answers

2532


What are the basic properties of signal flow graph?

683


what is differentila pilot supervision in the incomer control panel in the power station?

1625


how to modify DOL control panel into Delta Y connection?

1484


How should i design a 1ph & 3 ph transformer. Kindly let meknow all steps and formulaes related to design from scratch.

1520


Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m

2339


Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega

1362


pls tell me about ups internal connection & we have given only 3 phase supply to ups system how get 4 wire (R Y B N )

2287