In a Circuit how the MCB and Fuse ratings are calculated.
And shall the fuse follws the MCB or it is otherwise?

Answer Posted / viraj dua

Dear all there are two parameters for determining the
selection of MCB
1.Type of load-
Resistive(e.g Home circuits)-B curve MCB(operates @
3-5 times the rated current)
Inductive-Motors etc.-C curve MCB(operates @ 5-10
times the rated current)

Highly inductive load-Transformers etc.-D curve MCB
(operates @ 10-15 times the rated current)

2.current in the circuit.

Now you will find that curve along with rated current is
mentioned on the MCB e.g. C6(do not confuse rated current
with the breaking capacity which is the max. current CB can
witstand)
C6 means this MCB is usable for Inductive load where
Circuit can witstand upto 30 Amps and MCB should trip if
Current Reaches 30 amps(5times of 6Amps)-60 Amps(10 Times)

Rated current is mentioned as 'ln' in electrical literature.

Is This Answer Correct ?    47 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to calculate the formula of cable size if motor kw is given

1692


What is an ac motor?

686


what is the id1 & id2 setting in differential protection relay of CSPC?

2291


If oil and air can withstand a high MeV when used as an insulator in a transformer, what are the values of how high for each material?

1357


Where can i get practical knowledge of solar system?

972






what irequirment need to be followed when working on live equipment

1312


hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.

1515


Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?

1579


What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?

994


we have 2.2kw,Y,3000rpm motor but 6leads found in TB what happen if we connect in delta?

1260


Please clarify, 1. Is it required to lay two runs of GI wire along with Armoured LT cable if it is laid between one big mains (63Amps TPN SDF) to small main (32A TPN SDF) with proper glanding termination? 2. If the armoured cable with proper glanding is laid from DB to CNC machine, is it required to run two runs of body earthing to the Machine from DB? 3.If the armoured cable with proper glanding is laid from Substation to Hangar, distance is approx. 100 mtrs, is it required to do earthing at shop area though the primary termination at substation is earthed through gland.

1569


What is dynamo?How it works and what is the function of dynamo in a DG.

1591


Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?

1254


Why power factor should not be in leading (capacitive) mode of any load.

5866


Inductor and capacitor........power in one phase and ...... in it another phase.

1606