ON RADAR INTERFACE LEVEL TRANSMITTER IF DI-ELECRIC IS WRONG
WITH CONTINIUS PROCESS THAN HOW CAN INDENTIFY OR HOW CAN I
PUT NEW DI-ELECTRIC VALUE?(ROSEMOUNT-TDR-3300-COXIAL PROBE
TYPE)

Answer Posted / sam

You said interface level so I must assume you are measuring
oil and water. My experience is on the Khrone BM100 A but
your radar might be similar since the both use TDR technology.
The dielectric constant of crude is about 2 to 4 and water
is 80. The variance in dielectric constant will have a small
effect, so in order to find the right valve one quick way is
to use your sight glass to set the dielectric constants so
that the radar reads the same as the sight glass on the
water and oil. a Good average is normally 2,5 and 80.
Unfortunately this will not work unless you have setup your
Z/S parameters correctly.
If you are still having problems you need to do a complete
setup from scratch. In order to do this you need to get hold
of the design engineer's internal vessel drawings and look
what the calibrated span should be. What you are interested
in is the exact mm measurements from vessel bottom to Z/S
points or positions. From there it is just a matter of
taking exact measurements in the field of your vessel and
your radar installation and make yourself a neat, accurate
detailed drawing to indicate the design spec positions and
the actual position of your probe in relation to the vessel,
and put these measured values in the output 1 and output 2
parameters, keeping in mind zero position is measured from
the probe bottom up and 100% is also from the probe bottom
up and not from zero position up. So if you can see where
the design engineer have said zero should be and you can see
in exactly what position your probe is in relation to those
points it is a matter of calculating how high you need to
measure up from probe bottom to get to those Z/S points
marked by the design engineer. It takes a bit of
trigonometry to do but is easy enough.

Typically these parameters should look something similar to
this. Output 1 (Top product level) 4mA = 150mm, 20mA =
2500mm, Output 2 (Bottom product) 4mA = 150mm, 20mA = 2500mm.
Look strange I know but we have found it is better to set
them both the same instead of trying to set each one to it's
individual span. Both Spans are setup in reference to actual
vessel level %. Interface is also a actual level measurment
in relation to the whole vessel and not to just half the
vessel where for instance to where your wier plate is. If
you do this it will have the effect that you have a very
sensitive interface measurement to a slow level measurment
making your control very difficult. We have done it at one
point and it worked eventually, but it was very difficult to
optimize and get stable control, and even the smallest upset
will cause everything to go crazy again.

In this example the 150mm might be the mm you need to
measure from the probe bottom up to get to the Zero position
of the actual vessel as indicated by the design drawing and
the same with the 2500mm. Obviously just examples. This is
where your exact measurements in the field comes in.
NB!!
Also make sure you have the right probe length in the "tank
Height" parameter and not the real vessel height.
This probe length is normally stamped on the little spec
plate on the head by the supplier.
Good luck!

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how many types of spped sensors n vibration sensors?their basic principle n connection?

2069


what is the field bus calble ? what are diffrences in orang colur cable and black coular calble ?

2478


What is solenoid valve? Where it is used?

606


in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?

2692


what is sil (safety integrity level

2195






kindly sent some demo question and answer

1542


Can any body tell me about SAP MAINTINANCE MODULE. WHAT IS its function and application. And study material Source about it. I shall be very thankful.

1489


I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.

1158


we are having yokogawa centum cs3000 dcs in our power plant. i need some of the operator guides NOT to appear in HIS0163 AND HIS 0162 but it shoul appear in HIS0164 HOW TO DO IT?

2108


What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?

2628


What is feed factor and its Importance in cement industry? How we can solve feed factor?.

3087


What is the cascade control

988


Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....

1649


How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?

1589


find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s

1457