Why most of analog o/p devices having o/p range 4 to 20 mA and
not 0 to 20 mA ?
Answer Posted / ekailash
4-20 mA is a standard range used to indicate measured
values for any process. The reason that 4ma is chosen
instead of 0 mA is for fail safe operation.
For exa.- a pressure instrument gives output 4mA to
indicate 0 psi, up to 20 mA to indicate 100 psi, or full
scale. Due to any problem in instrument i.e. broken wire,
its output reducess to 0 mA. So if range is 0-20 mA then we
can differentiate whether it is due to broken wire or due
to 0 psi.
Is This Answer Correct ? | 9 Yes | 0 No |
Post New Answer View All Answers
how to find the capacitance value of the motor while running??
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
Comparision of Air break circuit breaker, SF6 Circuit breaker and vacuum circuit breaker.
at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)
in india per day how much power is generated including all power station
Suppose a 3 phase, 2 pole, 440V induction motor is driving a flywheel of 600mm diameter, 150kg mass. By using v-belt and pulley, the speed is increased to 4500 RPM. What will be the effect on motor current?
What the difference between three phase contactor (coil 110vac) & three phase SSR (control voltage 110Vac)? May I use contactor in place of SSR?
How to checked frequency drive output voltages?
what are the tests comes under the type test, what tests comes under routine tests.
Wt is the function of reactive power? How it generates & consume though resultant is zero?
In electrical locomotive engines, the DC series motors is being used as traction motor. But in new engines like in WAP7 & WAG9 the 3-phase squiral cage induction motors has replaced them. So can someone tell me the advantages of induction motor over dc seris motor in engines points of view....???
Why wind turbines wheels rotate constantly
This is reqd for a 1MW Solar power plant..We have 2DC outputs from the solar panels Connected to 2INVERTOR panels.. Output from invertor is 3ph,280v,500kva,50hz.These are connected to individual ACB.This has to be stepped up to 11KV ,1250KVA SYSTEM.Now can I use (1) one more ACBTO GIVE A COMBINED OUTPUT OF 1000KVA,280V & STEP UP THE OUTPUT BY USING a single two winding 3 ph transformer 11kv/1250kva. or (2)use the two outputs and connect to one three winding transformer of above rating..Pls suggestwith details.
What is the physical significant of power factor?
33kv Rated output avilable in market (any where in india)