what is restircted earth fault relay,how it works? what is
diffrance btwn normal earth falut relay & restricted earth
fault relay?
Answer Posted / javad ahamad
both e/f relays are different. consider an alternator, its
neutral is earthed through a
resistance inorder to limit earth fault current .then we
cant protect the 100% winding from
differential e/f relay only.because if an e/f occurs at
very near to neutral point the driving
current to operate relay will be very small. there for it
cant be sensed by this method,
we can protect up to 80%(approximate value.depent upon
resistance)only.at this situation
we r providing a restrcted e/f relay to protect the
remaining winding ie 20%.this relay
have very low current setting.by the combination of these
two we can protect 100% winding.
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
Define the term factor of inertia.
what is the criterion for selecting vector group of Transformers ? i mean how to decide vector group of Generator transformer, substation trasformer and transformer at consumer end
We have given to 3phase supply to ups system & how can coming netural
all the technical question with answers pleas send your email id ramar_eee@yahoo.com
Type of motor stater detail and working detail
what is the generator rating for 40 amp load of 3phase motor.?? 400v voltage of generator... plz tell me with formula its urgent...plzzz... and also tell me that this 40 amp at all phases mean 40 amp on red,40 amp on yellow,40 amp on blue...... or the total sum of that 3phase is 40 amp....
how to check regenerative load in drived motor
In how we connect watt meter for open & short circuit test of a single phase transformer.
can the measured percentage error during calibration of single phase energy meter be negative?
What is proportional controller?
What is zero of the system?
Give accurate definitions for these electric terms: Inductor Inductance Inductive Induction Reactance Reactive Esam Baraka ٢١ ساعة
Electrical Engineering
What is knee point voltage?
I PURCHASED A DEISEL GENARATOR SET OF AVR TYPE& RATING 125KVA BUT SOME TIMES THE OUTPUT VOLTAGE IS FLUCTUATING WHAT ARE THE PROBABLE REASONS GIVE ME