Why generally the Rating of Transformers are in additions
of 11 i.e. 11 kVA, 22 kVa, 33 kVA, etc........

Answer Posted / p. h. godavary

Here the question is not correct. Transformer ratings are never in multiples of 11.

It is the Generator voltages that are in multiples of Form factor 1.1(approx.). The voltages are 3300V, 6600V, 11000V. Consequently the normal distribution / transmitting voltages used are 3.3KV, 6.6KV, 11KV, 33KV, 66KV 110KV, .......

Form factor of an alternating current waveform is the ratio of the RMS (Root Mean Square) value to the Average Value of the waveform]. In the case of a sinusoidal wave i.e. , an analogue wave, the form factor is approximately 1.11

Is This Answer Correct ?    34 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The synchronous machine excitation system explain

1335


how the phase convertor changes the no. of phases

1550


What is meant by impedance? difference between high & low impedance ?

1570


Working of microwave oven?

1799


what is the mechanism of operation of brushless dc motor why is it more wexpensive then ordinary permanent magnet motors

1520






What is an iron loss or core loss pi?

636


is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.

1326


How many types of electrical earthing are there?

659


In Generator How suction compression power and exhaust works ?

1460


What is power in wattage of 8.5 TR AC

1197


what is the maximum temperature rating of a thhn insulated conductor?

1370


what is formula for calculate thermal overload in new numiricalrelay( not in bimetal relay)?

1799


Please clarify, 1. Is it required to lay two runs of GI wire along with Armoured LT cable if it is laid between one big mains (63Amps TPN SDF) to small main (32A TPN SDF) with proper glanding termination? 2. If the armoured cable with proper glanding is laid from DB to CNC machine, is it required to run two runs of body earthing to the Machine from DB? 3.If the armoured cable with proper glanding is laid from Substation to Hangar, distance is approx. 100 mtrs, is it required to do earthing at shop area though the primary termination at substation is earthed through gland.

1576


What is tan delta & PPM in transformer? and whats its IS value?

1599


What are the limitations of Kirchoff's laws?

1128