Why generally the Rating of Transformers are in additions
of 11 i.e. 11 kVA, 22 kVa, 33 kVA, etc........
Answer Posted / p. h. godavary
Here the question is not correct. Transformer ratings are never in multiples of 11.
It is the Generator voltages that are in multiples of Form factor 1.1(approx.). The voltages are 3300V, 6600V, 11000V. Consequently the normal distribution / transmitting voltages used are 3.3KV, 6.6KV, 11KV, 33KV, 66KV 110KV, .......
Form factor of an alternating current waveform is the ratio of the RMS (Root Mean Square) value to the Average Value of the waveform]. In the case of a sinusoidal wave i.e. , an analogue wave, the form factor is approximately 1.11
| Is This Answer Correct ? | 34 Yes | 3 No |
Post New Answer View All Answers
Percentage losses in power generation?
What do you mean by ratio correction factor of instrument transformer?
Please give me a erda placement paper
how many Classification of fire extinguisher
Why the power factor improvement is so important in industrial loads
What are the three constants associated with a steady state error?
What is the reason behind current flow(20 A) in amain earth cable of an SMDB? Is cuurent flow(45A etc) through a neutral cable acceptable?
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
Draw a block diagramof Three UPS systems connected in Parallel mode?
Different STANDARDS (BS, IS, IEC etc) gives different informations on CT specification. How they correspons w r t each other (i.e I mean to say BS provides "knee point voltage" but IS does not, then how can i select CT)
difrent between vcb acb sf6 and mccb breakers
Why is water motor not taking the pressure? what is the problem?
what is the Connected Load (kW) or Contract Demand (kVA)of mahindra nasik plant??
diameter of cable and core is doubled then the value of capacitance is
A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is