i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?

Answer Posted / k.sreenivasan

Go to the field and check the local indication in the
transmitter.(normally it is in either engg. units or as
percentage)
If it is zero ,then the problem is in the sensor or
terminal connection, because most of the current generation
transmitters are highly accurate and have longer stability
periods.
Suppose local reading is ok,then check the DCS analog input
card for any fault condition and clear it.Normally this
situation is rare.

Is This Answer Correct ?    24 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain working principle of lvdt?

636


the 3 most common transmitter protocol being in refinery or qatar gas and aramco.

2491


How to Calibrate Radar Level Transmitter in Field

736


What is the use of double seated valve?

739


i have done DAE in Instrumentation and Process Control. i have applied for an apprentice training in chemical company after three day my interview will be conduct but i need more information about industrial process control and controller. my e mail is imran_dilsetu@yahoo.com please tell me interview question relative to instrumentation ?

1878






any body please send me the old question papers of ongc test.

1677


Explain types of valves?

668


plz tell me clearly about PID.."when v have to change I value,D value,GAIN??

1696


How will you calibrate PID controller? explain with example.

1977


how to convert cubic metre per hour to newton cubic metre per hour

1587


How to Calibrate Ultrasonic flow Transmitter in Field

801


what is easiest way to read STL language in PLC?

2664


Which type of pressure can be measured by primary elements?

620


what is controlling card in dcs? how u measure dcs memory?what is bus in dcs?how u know dcs speed n ehternet speed?

1513


how can use ram

1489