i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?
Answer Posted / k.sreenivasan
Go to the field and check the local indication in the
transmitter.(normally it is in either engg. units or as
percentage)
If it is zero ,then the problem is in the sensor or
terminal connection, because most of the current generation
transmitters are highly accurate and have longer stability
periods.
Suppose local reading is ok,then check the DCS analog input
card for any fault condition and clear it.Normally this
situation is rare.
Is This Answer Correct ? | 24 Yes | 1 No |
Post New Answer View All Answers
Explain working principle of lvdt?
the 3 most common transmitter protocol being in refinery or qatar gas and aramco.
How to Calibrate Radar Level Transmitter in Field
What is the use of double seated valve?
i have done DAE in Instrumentation and Process Control. i have applied for an apprentice training in chemical company after three day my interview will be conduct but i need more information about industrial process control and controller. my e mail is imran_dilsetu@yahoo.com please tell me interview question relative to instrumentation ?
any body please send me the old question papers of ongc test.
Explain types of valves?
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
How will you calibrate PID controller? explain with example.
how to convert cubic metre per hour to newton cubic metre per hour
How to Calibrate Ultrasonic flow Transmitter in Field
what is easiest way to read STL language in PLC?
Which type of pressure can be measured by primary elements?
what is controlling card in dcs? how u measure dcs memory?what is bus in dcs?how u know dcs speed n ehternet speed?
how can use ram