Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the function of anti-pumping in circuit breaker?

Answer Posted / kayode j.

The anti-pumping relay is a device in circuit-breaker whose
function is to prevent multiple breaker closures. For
instance, if the operator gives the closing command to the
breaker by pressing the close button and the breaker
closes. However, a fault in the system causes the breaker
to trip. Since the close command is still in the pressed
condition, there is a chance of the breaker closing again
and being tripped by the relay multiple times. This can
damage the closing mechanism of the breaker. The anti-
pumping relay prevents this by ensuring that the breaker
closes only once for one close command from the control
panel.

Is This Answer Correct ?    249 Yes 12 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?

2800


the grid connection required for a 50 MegaWatt fotovoltaic powerplant is higher or lower than 35kv (high or medium tension)?

1861


How to calculate multiplying factor of dc energy meter

1677


what is sevice settings for mccb?How can be it setted?

2005


What is the function of RCBO? What are the different sensitivity ratings & each application?

2829


In ACS 1000 drive we are using 12 pulse converter,why don't use 3 pulse converter.

2026


what is the maximum permissible limit value of leakage current and leakage counter reading to replace lightining arrester?

5146


why we have and use 3 phase not 2 or 4 or other in power system?

2128


What will happen if the d.c. Machine is operated below rated speed?

1249


Are Refrigerators & Deep Freezers the Inductive load ? How to calculate the Power Factor & hence the Output Power for them ?

5115


determine two methods to find loose connection in operational electrical system?

1693


Where I can get the sample question for post of Junior engineer electrical-II For RRB Bhubaneswar.

2190


In convertor can we use rectifier thyristor in place of invertor thyristor with explain.

1823


In a tap changing transformer where is the tap connected, is it connected in the primary side or secondary side?

1150


What happens if i apply 500V to 440V rotary Switch ?

1837