HOW TO CALCULATE CT AND VT RATIO IN PRTECTION AND METERING?
Answer Posted / naveen singh
To find out Multiflying factor
1) If meter CT Ratio is not given then CT Ratio provided in
the panel has to be considered. Example if CT Ratio in the
Metering Panel is 600/5 then the M.F is 120.
2) If CT Ratio is mentioned in the Meter then Meter CT
Ratio / CT Rating Provided in the Metering panel.
Example If the CT Ratio of the Meter is 600/5 and CT
Provided in the Panel 800 /5 then Multiplying Factor will
be 600/5 /800/5. i.e., 600/800 then M.F is 3/4 (0.75)
3)In addition to this any Multiflying factor is mentioned
in the Meter then it has to be multiplied. Example if Meter
CT Ratio is 600/5 and Panel Ratio is 800/5 and M.F
mentioned in the Meter is 3 then the M.F will be (600/800)
*3. i.e., 0.75*3 =2.25
Is This Answer Correct ? | 20 Yes | 8 No |
Post New Answer View All Answers
How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer
Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?
What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.
how to avoid Saturation in C.T?
If i have two 3000 kW motors and the whole facility requires a 10 MVA transformer. What would be better installing two 5 MVA transformers(one for 1 motor ) or just a single 10 MVA transformer for both of them. Give reasons for your answer.
AL=0B9H,bl=75H, ADD AL,BL AL=____________? CF________? OF___________?
What type of wiring series or parallel is used for conventional and addressable type FAS & why?
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???
Why a Permanent Magnet Generator has higher frequency as compared to frequency of main alternator?
delta motor winding resistance I take normally single winding is 2.5, which value is came delta connection ie RY ?
How to calculate total harmonic distortion level(THD) in VFD? and how can we reduce harmonics?
What are the special cables required for explosion proof wiring?
can anyone give an idea about dia calculation in cold rolling mill
What is the armature mmf in a D.C machine?
what will happen when the dc supply is given to the capacitor?