Answer Posted / ramji
Mr.Sudheer u r not clear.U r telling the condition after DG
starting only, not during running.
Mr.Shri can u please explain me how the voltage will be
fluctuating if the AVR is OFF.
In parallel mode if the AVR of the suspected DG
fails, then the reactive power of the particulat DG gets
reversed because the DG will be out of its running
quadrant.Since the reactive power is reversed, DG will be
trip on under reactance.Also if it is not tripped, its
outgoing current will be increased, so it will trip on Over
current.
In island mode if the AVR of suspected DG set
fails, then the loads connected to it will be thrown off
immediatly and the DG may trip on prime mover overspeed due
to sudden throw of load or undervoltage protection on DG.
Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
H.t motor 6600 volt to same motor lt supply 440volt supply applyed to h.t motor to effect....
For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?
if we look on phasor of the transformer vaoltage is 180 oppsite at primary and the secondary so to improve a power factor is secondary should kept negative to improve it primary side means is -.90 became +.90 at other side
how can i get an electrical c-certificate?
What is the use of iron core in a transformer?
What is the maximum and minimum rating of UPS?
For a stable system, where should the poles of a system be in a root loci plot?
You are of electrical field and you are going for software? Why
How it can worked plc based electrical system And which type of software using.
how we can decide that what value of ht line will come to any commercial building? (ans except According to the building load)
1)What is a Triode? What are its uses? 2) What is a Triac? 3) What is a Thyristor?
explain different types of d.c motors?
What will happen to the protection and metering, if the polarity of a single or two PT/PTs in three phase system is reversed? Please provide reference if any.
State kirchoff current law?
In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..