what is the difference between earthed and unearthed cable?
Answer Posted / n. ramesh
In unearthed cables (usually ht cables), the core
insulation will be rated for Uphase-phase as the healthy
phase conductors will be at √3 times Uphase-neutral with
respect to earth in case of a single phase to earth fault
(when laid in ground). Whereas in the case of earthed
cables, the healthy phase conductors will be at Uphase-
neutral with respect to earth even when there is single
phase to earth fault. Hence, in the case of earthed
cables, the core insulation will be rated for Uphase-
neutral.
Further, in earthed cables, a current equal to the current
through the phase conductors will flow through the shield,
which will heat up the shield. Hence, current rating of
cables meant for earthed application will be slightly lower
than the current rating of cables meant for unearthed
application for the same conductor cross sectional area.
Generally 6.6 kV and 11kV systems are earthed through a
neutral grounding resistor and the shield and armour are
also earthed, especially in industrial power distribution
applications. Such a case is similar to an unearthed
application but with earthed shield (some times called
solid bonding). In such cases, unearthed cables may be
used so that the core insulation will have enough strength
but current rating is de-rated to the value of earthed
cables.
But it is always better to mention the type of system
earthing in the cable specification when ordering the
cables so that the cable manufacturer will take care of
insulation strength and de-rating. Also it is better to
use the cables for the type of system earthing they are
meant for.
Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
what is gridrotor resistance starter
whatis the commertial spec. of distribution boards ?
Describe Non I.S. Earth System and why is it used?
why on axial hitting up of air blast on hydrogen produced in oil circuit breaker,temperature rises of the core of the arc?
Whether should be the oil level in OCTC transfomer? It should be upto winding immersed completely or should be upto tap changer s/w? How it will affect the performance of the transformer. Rating may be 33KVA
how braking & making capacity of circuit breaker is calculated?
High voltage test procedure of in swgr board. why should measure millivolt drop on testing time?
What is the Surge for 1.1 Phase Induction Motor(For Eg.1Hp) 2.3 Phase Induction Motor(For Eg.1Hp) 3.AirConditioner(For Eg 1Ton) 4.Refrigerator(For Eg 180Ltr or 160kW) 5.Induction Cooker 4. Ceiling Fan
What is slip in an induction motor?
IN induction motor pf is increased using capacitors.what will be the effect on motor and system when very large capacitor is accidently installed and pf goes leading.
HOW TO CALCULATE S/C,O/C,E/F OF ACB.
We normally make oil soak pits under Transformers. Oil from soak pit goes to collection pit. We provide granules/pebbles under transformers. My question is weather granules/ pebbles to be filled in soak pit or not? if yes upto what level?
how a flip flop can be used as a latch?
what do you mean by every IC 74 first digit.why are you using this no.why not using another no.
What are chief characteristics of state-space method and its techniques ?