What is loop or pigtail in an impulse line?
Answer Posted / haridass_drm
My friend, Mr. K. Thirunathan Ntpc Ramagund, all your
points are correct, except
3.FINALLY IT REDUCES HIGH PRESSURE INTO LOW PRESSURE AND
AVIOD VIBRATION IN IMPULSE LINES.
In this point, avoiding vibration is ok, but how the high
pressure will get reduce to low pressure? If like, how can
we use that pigtail for high range pressure
gauge/transmitter?
According to me, this pigtail will be used to avoid the
sudden pressure impact on the gauge/transmitter, created in
the process where it fixed. Because the boiler/vessel/steam
line will be high pressurized, so there is the chances for
sudden variation, the pigtail will safe the instruments if
it used.
| Is This Answer Correct ? | 18 Yes | 4 No |
Post New Answer View All Answers
Draw symbols of the following :
in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?
What is Predictive Maintenance
Can anybody tell me how to select the size of earthing cable for DCS & PLC system.Please tell me any relevant answer here or mail it to me.
Conversions
how to convert MA in to measuring values..and how mwasuring values into MA ?..plz ansr.i have intervw
How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?
draw the block diagram of a level transmitter ?
what is wave length were using ?
why we are using magnet for calibration of gas detector?
few questions on RS 232,1 question on relationship of impedance and turns ratio, many questions on flowmeters
How is PH sensor works ?
i have done DAE in Instrumentation and Process Control. i have applied for an apprentice training in chemical company after three day my interview will be conduct but i need more information about industrial process control and controller. my e mail is imran_dilsetu@yahoo.com please tell me interview question relative to instrumentation ?
Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram
What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem?